1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  <20112012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  <20112012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE: problem with ip330-2-6 (A/D converter board) scanmode functionality to switch modes at runtime
From: <[email protected]>
To: <[email protected]>
Date: Mon, 4 Jul 2011 08:48:00 +0000

When I was using the ip330 in Continuous mode I found it necessary to set the gain a couple of times in my startup file in order to get it to run:

 

record(longout,"BL18I-EA-IONC-01:IGain")

{

        field(PINI,"YES")

        field(VAL,"0")

        field(DTYP,"asynInt32")

        field(OUT,"@asyn(ip330b 0)GAIN")

}

 

And in the startup file:

 

dbpf ("BL18I-EA-IONC-01:IGain","1")

dbpf ("BL18I-EA-IONC-01:IGain","0")

 

Note sure if this is relevant to you but it may be worth trying when you switch back to continuous mode.

 

Pete Leicester

Diamond Light Source

 

From: [email protected] [mailto:[email protected]] On Behalf Of Jay Steele
Sent: 29 June 2011 19:20
To: [email protected]
Subject: problem with ip330-2-6 (A/D converter board) scanmode functionality to switch modes at runtime

 

Hi EPICS folks,

     I’m seeing a problem with the EPICS module for the VME ADC board IP330, software version 2-6. I’m trying to switch between Burst Continuous and Burst Single modes for step scanning and hardware-synchronized fly scanning, respectively, at run time. When I process the provided ScanMode record, the board gets stuck in Burst Single mode no matter if I’m setting the Burst Continuous mode (value 3) or Burst Single mode (value 4).

 

    Has anybody else been successful at switching modes at run time for the IP330 board using this software?

 

Thanks,

Jay Steele

Xradia Corporation

 


The information in this email, including any attachments, is confidential and intended only for the recipient(s) listed. Any use of this email for any other purpose is prohibited. If you have received this email in error, please notify me immediately by reply email, delete this email, and do not disclose its contents to anyone.


 

-- 

This e-mail and any attachments may contain confidential, copyright and or privileged material, and are for the use of the intended addressee only. If you are not the intended addressee or an authorised recipient of the addressee please notify us of receipt by returning the e-mail and do not use, copy, retain, distribute or disclose the information in or attached to the e-mail.
Any opinions expressed within this e-mail are those of the individual and not necessarily of Diamond Light Source Ltd.
Diamond Light Source Ltd. cannot guarantee that this e-mail or any attachments are free from viruses and we cannot accept liability for any damage which you may sustain as a result of software viruses which may be transmitted in or with the message.
Diamond Light Source Limited (company no. 4375679). Registered in England and Wales with its registered office at Diamond House, Harwell Science and Innovation Campus, Didcot, Oxfordshire, OX11 0DE, United Kingdom
 



Replies:
RE: problem with ip330-2-6 (A/D converter board) scanmode functionality to switch modes at runtime Jay Steele
References:
problem with ip330-2-6 (A/D converter board) scanmode functionality to switch modes at runtime Jay Steele

Navigate by Date:
Prev: RE: SNL seq-2.0.13 on Linux 64 bits: not all monitored PVs receive their first monitor event Utzel Nadine
Next: CAJ maintainer, anyone? Till Straumann
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  <20112012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: problem with ip330-2-6 (A/D converter board) scanmode functionality to switch modes at runtime Jay Steele
Next: RE: problem with ip330-2-6 (A/D converter board) scanmode functionality to switch modes at runtime Jay Steele
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  <20112012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 18 Nov 2013 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·