Experimental Physics and Industrial Control System
|
Hi Priya,
Return 2, instead of 0, from read_ai. That tells the record that you put the value in VAL. If you return 0, you are telling the record you put the value in RVAL, and that the record should convert RVAL to get VAL.
See "Device Support Routines" in
Tim Mooney ( [email protected]) (630)252-5417
Software Services Group (www.aps.anl.gov)
Advanced Photon Source, Argonne National Lab
Hello,
I am trying to write the value into val field of ai record from device support.I am beginner in EPICS so I have no idea about this. But i have tried then i got the errors at run time please help me.I am attaching code file.
Thanks in advance...
|
- Replies:
- Re: related to coding priya tiwari
- References:
- related to coding priya tiwari
- Navigate by Date:
- Prev:
related to coding priya tiwari
- Next:
Re: related to coding priya tiwari
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
<2015>
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
related to coding priya tiwari
- Next:
Re: related to coding priya tiwari
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
<2015>
2016
2017
2018
2019
2020
2021
2022
2023
2024
|
ANJ, 16 Dec 2015 |
·
Home
·
News
·
About
·
Base
·
Modules
·
Extensions
·
Distributions
·
Download
·
·
Search
·
EPICS V4
·
IRMIS
·
Talk
·
Bugs
·
Documents
·
Links
·
Licensing
·
|