1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  <20152016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  <20152016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Looking for Allen Bradley PLC5 Ethernet support
From: David Morris <[email protected]>
To: Paul Sichta <[email protected]>
Cc: "[email protected]" <[email protected]>
Date: Thu, 19 Feb 2015 22:21:05 -0800
We replaced the PLC5 versions for our TR13 cyclotron with Ethernet capable ones, PLC5/20E and PLC5/40E. This allowed us to transition from a DH+ based console to EPICS without cutting the cord. I used John Sinclair's driver from SNS but heavily modified it to handle the memory arrangement in the PLC,as the SNS driver assumes a contiguous block of data transfer memory, and the TR13 used randomly scattered bits in many words. We could not change the PLC code due to licensing. 

I can provide a tarball. 

Dave Morris
TRIUMF


Sent from my iPhone

On Feb 19, 2015, at 6:44, Paul Sichta <[email protected]> wrote:

Mike,
We are using OPC server with  RSLinx Gateway to comm PLC5 with the IOC.  The guy who did that recently left but I could dig up some details if you want to pursue that.

-ps


On Thu, Feb 19, 2015 at 8:47 AM, Mike Westfall <[email protected]> wrote:
Hello,
We would like use the Ethernet version of AB/PLC5 PLCs.
Has anyone implemented EPICS device support for these?
Maybe a StreamSDevice protocol file?


--
Mike Westfall
Gemini Observatory
Colina El Pino S/N, Casilla 603
La Serena, Chile
Tel: +56 51 2205625


References:
Looking for Allen Bradley PLC5 Ethernet support Mike Westfall
Re: Looking for Allen Bradley PLC5 Ethernet support Paul Sichta

Navigate by Date:
Prev: FW: Looking for Allen Bradley PLC5 Ethernet support Stevens, James
Next: Re: using EPICS code with HTTP port Dirk Zimoch
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  <20152016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: FW: Looking for Allen Bradley PLC5 Ethernet support Stevens, James
Next: Can you stop script execution with adPython for AreaDetector? Isabella Rey
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  <20152016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 16 Dec 2015 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·