Hi Zhang,
One way would be to introduce a fanout record with LNK1 and LNK2 pointing at records A and B, and SELM set to "Specified". Then you would have a fift calcout record that writes 1 or 2 to the SELN field of the FANOUT, depending on the bo record value.
Hope this helps, Isabella