Hi Tasaddaq,
You can use the OOPT field to specify when the output link should be executed. c.OOPT="When Non-zero"
Tim Mooney ( [email protected]) (630)252-5417
Software Services Group (www.aps.anl.gov)
Advanced Photon Source, Argonne National Lab
Dear all
I have three records, when the value in the record "b" is "1" the value in the record c is calculated and the record d is updated as well. Upto this the things are working fine. But I want one more thing that when the b=0, the value of record "c" should become
the zero (that is happening) but it should not send the value zero to the record d means at b=0 record c should be updated but it should not update the record d. I want to keep the last value of record d so that when b=1 again then record d should start from
the last value that it will hold. Please tell me how to do this?
record (bi,"b"){
field(FLNK, "c")
}
record (calcout, "c"){
field(SCAN, "1 second")
field(INPA, "c")
field(INPB,"b")
field(INPC,"1")
field(CALC,"B=1?A+C:0")
field(OUT,"d PP")
}
record(calcout, "d"){
field(INPA, "c")
field(INPB,"1")
field(CALC,"A+B")
}
regards,
Tasaddaq
|
- References:
- how NOT to update the record Tasaddaq Khan
- Navigate by Date:
- Prev:
how NOT to update the record Tasaddaq Khan
- Next:
how to write array data to waveform record in cothread? Silver
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
<2015>
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
how NOT to update the record Tasaddaq Khan
- Next:
RE: how NOT to update the record Mooney, Tim M.
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
<2015>
2016
2017
2018
2019
2020
2021
2022
2023
2024
|
ANJ, 16 Dec 2015 |
·
Home
·
News
·
About
·
Base
·
Modules
·
Extensions
·
Distributions
·
Download
·
·
Search
·
EPICS V4
·
IRMIS
·
Talk
·
Bugs
·
Documents
·
Links
·
Licensing
·
|