Experimental Physics and
| |||||||||||||||
|
Mark is right. It all depends, as always. ;-) Cheers, ~Ralph On Tue, Jul 18, 2017 at 1:35 PM, Mark Rivers <[email protected]> wrote: This only works if the device support reads the value into RVAL and returns 0, rather than 2 (do not convert). This means your value in watts would need to be an integer, because RVAL is a long. So if your device support is reading a double directly into VAL and returning 2 then you cannot do the scaling in the ai record, you need to do it in an external calc record.
| ||||||||||||||