1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  <20182019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  <20182019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Controling a slit system with 2 hard and 4 soft motorrs
From: Torsten Bögershausen <[email protected]>
To: "Mooney, Tim M." <[email protected]>, "Goetze, Kurt A." <[email protected]>, "[email protected]" <[email protected]>
Date: Thu, 7 Jun 2018 19:45:06 +0200


On 07/06/18 19:16, Mooney, Tim M. wrote:
Hi Torsten,


Yes, we can certainly go over the database.


I think the link alarm is not a problem.  If the soft motor record processes and gets a value from a record with UDF==1, it should be in link alarm.

Yes, that is working.

The problem/issue I have is to get the soft motor out of the link alarm.
It seems as if we need a record-processing, which does not happen.



Tim Mooney ([email protected]) (630)252-5417
Beamline Controls Group (www.aps.anl.gov)
Advanced Photon Source, Argonne National Lab

________________________________
From: Torsten Bögershausen <[email protected]>
Sent: Thursday, June 7, 2018 10:52:20 AM
To: Mooney, Tim M.; Goetze, Kurt A.; [email protected]
Subject: Re: Controling a slit system with 2 hard and 4 soft motorrs

Hej Tim and all,

We actually got the slit working in the motion controller.
I have, anyway, used the 2slit.db, mainly for testing & learning.

For the motor module, I use a patched version, which keeps the record
in UDF state, until the poller has really talked to the controller.
As a result, the soft motors sometimes (depending on the timing)
stay in "link alarm".
A movement will make the alarm disappear.

Do you think we can go through the db file next week,
some help is wanted.

BR
/Torsten



On 08/03/18 18:20, Mooney, Tim M. wrote:
There is also, in the optics module, 2slit_soft.vdb, which uses soft motor records, instead of ao records, for center and width.


Tim Mooney ([email protected]) (630)252-5417
Beamline Controls Group (www.aps.anl.gov<http://www.aps.anl.gov>)
Advanced Photon Source, Argonne National Lab

________________________________
From: [email protected] <[email protected]> on behalf of Goetze, Kurt A. <[email protected]>
Sent: Thursday, March 8, 2018 10:51:13 AM
To: Torsten Bögershausen; [email protected]
Subject: RE: Controling a slit system with 2 hard and 4 soft motorrs

Hi Torsten,

The synApps optics module has support for this type of thing:

https://github.com/epics-modules/optics/blob/master/opticsApp/Db/2slit.db

Kurt

-----Original Message-----
From: [email protected] [mailto:[email protected]] On Behalf Of Torsten Bögershausen
Sent: Thursday, March 08, 2018 10:40 AM
To: [email protected]
Subject: Controling a slit system with 2 hard and 4 soft motorrs

Hej motorists,

I recently learned about the transform record, which can be used to control a slit with 2 physical axes in the way that you can set the values for GAP and CENTER and the position of the physical blades are calculated. (Or vice versa)

Does anybody have a super-duper-luxus template file which uses 4 soft motors together with some calc and transform records ?

Thanks in advance
/Torsten



References:
Controling a slit system with 2 hard and 4 soft motorrs Torsten Bögershausen
RE: Controling a slit system with 2 hard and 4 soft motorrs Goetze, Kurt A.
Re: Controling a slit system with 2 hard and 4 soft motorrs Mooney, Tim M.
Re: Controling a slit system with 2 hard and 4 soft motorrs Torsten Bögershausen
Re: Controling a slit system with 2 hard and 4 soft motorrs Mooney, Tim M.

Navigate by Date:
Prev: Re: Controling a slit system with 2 hard and 4 soft motorrs Mooney, Tim M.
Next: Re: MVME3100 FPU Support on RTEMS 4.10.2 Matt Rippa
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  <20182019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Controling a slit system with 2 hard and 4 soft motorrs Mooney, Tim M.
Next: Mako G-234B (6408) - Prosilica Area Detector question Mark Engbretson
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  <20182019  2020  2021  2022  2023  2024