Experimental Physics and Industrial Control System
|
Hi Mark, This is not working. I send commands and I don't get a response. The notes on the RS-232/GPIB converter says it needs full flow control. My startup script has these commands to talk to the Moxa:
drvAsynIPPortConfigure("serial2", "gsets11:4002 COM", 0, 0, 0)
asynSetOption(serial2,0,baud,19200)
asynSetOption(serial2,0,bits,8)
asynSetOption(serial2,0,stop,1)
asynSetOption(serial2,0,parity,none)
asynSetOption(serial2,0,crtscts,Y)
Any idea why this would not work, when it did work with a local serial port?
I am baffled. You can configure the Moxa box remotely by setting the asyn options? Honestly, I would never ever have expected that to work. Is that a Windows thing? Wait... or does the Moxa emulate a modem - AT commands and all? Like Maren, I would always use the web interface on the Moxa to configure the serial line, before connecting with a telnet client to test and finally have the asyn IOC connect.
Really interesting. ~Ralph
- Replies:
- Re: GPIB remote control Cobb, Tom (DLSLtd,RAL,LSCI) via Tech-talk
- Re: GPIB remote control Maren Purves via Tech-talk
- References:
- GPIB remote control Mark Rivers via Tech-talk
- Navigate by Date:
- Prev:
Re: GPIB remote control Maren Purves via Tech-talk
- Next:
Re: GPIB remote control Cobb, Tom (DLSLtd,RAL,LSCI) via Tech-talk
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
<2020>
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: GPIB remote control Michael Davidsaver via Tech-talk
- Next:
Re: GPIB remote control Cobb, Tom (DLSLtd,RAL,LSCI) via Tech-talk
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
<2020>
2021
2022
2023
2024
|
ANJ, 06 Nov 2020 |
·
Home
·
News
·
About
·
Base
·
Modules
·
Extensions
·
Distributions
·
Download
·
·
Search
·
EPICS V4
·
IRMIS
·
Talk
·
Bugs
·
Documents
·
Links
·
Licensing
·
|