Thank you, Yong, for testing and fixing issues.
Yong added “ bpm_DBD += PVAServerRegister.dbd” and enabled PVA.
$pvget SR-C14:BxBPM-1:Pos:X-I
SR-C14:BxBPM-1:Pos:X-I 2023-08-30 09:37:21.003 5.02208
Kiman
From: Hu, Yong <yhu at bnl.gov>
Sent: Tuesday, August 29, 2023 10:02 PM
To: Ha, Kiman <kha at bnl.gov>; tech-talk at aps.anl.gov
Subject: Re: PV Access timeout
Kiman, I can help you with this. My guess is that some PVA variables need to be re-configured due to our internal networks. --Yong
Michael,
I attempted to enable PVA to the existing pscDrv IOC but got a timeout error.
I just added two lines in Makefile and compiled them correctly.
#Adding Makefile
bpm_DBD += qsrv.dbd
bpm_LIBS += qsrv
$ pvget SR-C14:BxBPM-1:Pos:X-I
Timeout
$ caget SR-C14:BxBPM-1:Pos:X-I
SR-C14:BxBPM-1:Pos:X-I 5.02535
Did I miss something, and how do I check that the PVA server is running?
Thanks,
Kiman