1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  <2024 Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  <2024
<== Date ==> <== Thread ==>

Subject: Re: mvme3100 epics and control motor
From: Heinz Junkes via Tech-talk <tech-talk at aps.anl.gov>
To: 백호령 <holyeongbaeg at gmail.com>
Cc: tech-talk at aps.anl.gov
Date: Wed, 24 Jan 2024 10:24:04 +0100
Hello Baeg,
we use MVME3100 and MVME6100 in combination with the MAXv controller cards.
Both cpu’s with RTEMS5/6 and Epics7. In my opinion, the clock frequency of the CPU is irrelevant
as the motor 'intelligence' is on the MAXv card.

Heinz
------------------------------------------------------------------------------
Fritz-Haber-Institut    | Phone:         (+49 30) 8413-4270
Heinz Junkes             | Fax (G3+G4):   (+49 30) 8413-5900
Faradayweg 4-6        | VC: https://zoom.fhi.berlin/junkes
D - 14195 Berlin        | E-Mail:        junkes at fhi-berlin.mpg.de
------------------------------------------------------------------------------

> On 24. Jan 2024, at 02:43, 백호령 via Tech-talk <tech-talk at aps.anl.gov> wrote:
>
>
> Hello, I'd like to ask you about mvme3100 and epics versions and synapses versions.
> First, we configured the motor control system using the mvme6100 and maxv controller.
> However, we want to build a new motor control system as the production of the mvme6100 is lost.
> Currently, the available cpu is mvme3100, and this cpu is compatible with version 6.9 of vxworks, so we want to select it.
> However, before I choose, I would like to ask for your advice if the mvme3100 model is also available in epics base 3.15.9 and synApps 6-1, and motor-R7-1.
>
> And, for MME6100, the clock count is 1.2Ghz, and for MME3100, the clock count is 500Ghz. The clock count is more than double, is there any problem with motor control?
>
> There are many things I don't know because I'm a junior in the field. Please give me advice and teaching.
>
> Best&Regards.
> Baeg

Attachment: smime.p7s
Description: S/MIME cryptographic signature


References:
mvme3100 epics and control motor 백호령 via Tech-talk

Navigate by Date:
Prev: Re:Re:Re: RE: A question on asyn application cxy via Tech-talk
Next: Re: mvme3100 epics and control motor Ralph Lange via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  <2024
Navigate by Thread:
Prev: mvme3100 epics and control motor 백호령 via Tech-talk
Next: Re: mvme3100 epics and control motor Ralph Lange via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  <2024
ANJ, 24 Jan 2024 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·