Experimental Physics and Industrial Control System
|
> Questions:
> 1. how does one (especially the client) know that the limits are really set? And not default values.
> 2. if it performs a check that HOPR!=LOPR then what if one defines an upper limit (but does not need a low one) and vice-versa.
to 1.)
As pointed out previously: The client does not know it.
Of course DRVH/L are already handled by the record: if DRVH=DRVL=0 then only a "0" can be written to the hardware
But HOPR and LOPR are not used by all clients.
If you want to use them in any client, take care that they are set for ALL records that are meant to be used by any client.
to 2.)
The only way to allow HOPR and LOPR to be set individually would be to change the default: HOPR=+Inf and LOPR=-Inf.
But this is not really useful: e.g. if you want to present a control slider you need two limits to just show it.
And if just one client has a problem with one unset limit, then you'll need to set all limits.
Just drop the idea of not setting HOPR or LOPR for any relevant PV.
Every PV has to have a valid range.
Andreas
--
Dr. Andreas Luedeke, SLS Operations Manager, Tel:+41-56-3104002
[email protected], http://people.web.psi.ch/luedeke
- Replies:
- RE: DRVL, DRVH, HOPR, LOPR Abadie Lana
- Re: DRVL, DRVH, HOPR, LOPR Dirk Zimoch
- Navigate by Date:
- Prev:
RE: DRVL, DRVH, HOPR, LOPR Dalesio, Leo
- Next:
RE: DRVL, DRVH, HOPR, LOPR Abadie Lana
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
<2012>
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: mvme6100 HW issues? chris.colborne
- Next:
RE: DRVL, DRVH, HOPR, LOPR Abadie Lana
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
<2012>
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
|
ANJ, 18 Nov 2013 |
·
Home
·
News
·
About
·
Base
·
Modules
·
Extensions
·
Distributions
·
Download
·
·
Search
·
EPICS V4
·
IRMIS
·
Talk
·
Bugs
·
Documents
·
Links
·
Licensing
·
|