1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: help with StreamDevice
From: "Brown, David L." <[email protected]>
To: "[email protected]" <[email protected]>
Date: Tue, 25 Jun 2013 08:45:40 -0400
Hey, guys,

I'm new to the whole StreamDevice thing, but I've been attempting to utilize this functionality over the past month or so to connect to a Tektronix AFG3200B.  I have experienced this weird phenomenon, though, where I get the following error:

Bad init_rec return value  PV: ICS_Devel:AFG3000:cwfreq1_set ao: init_record
2013/06/25 08:28:55.275 L0 vxiConnectPort error 192.168.200.137: RPC: Remote system error - Connection timed out

2013/06/25 08:29:16.279 L0 vxiConnectPort error 192.168.200.137: RPC: Remote system error - Connection timed out

When I go to the device, itself, it has an IP address through DHCP, and appears to be normal.  A netstat command yields the following results:

netstat -a -n | fgrep 200.137tcp        0      0 192.168.200.100:60949       192.168.200.137:111         TIME_WAIT
tcp        0      0 192.168.200.100:35230       192.168.200.137:111         TIME_WAIT
tcp        0      0 192.168.200.100:50146       192.168.200.137:1008        ESTABLISHED
tcp        0      1 192.168.200.100:50215       192.168.200.137:1008        SYN_SENT

This usually happens after repeated attempts to reboot my soft ioc (after editing db records and the protocol file).  I don't think the problem is in my files because I can power cycle to device and reboot my soft ioc to reconnect.  The only thing I can imagine is that the generic ASYN driver I'm utilizing (version 4-12 or 4-14) has a bug in it.  Can you guys offer any suggestions?  I'm running EPICS version R3.14.8.2.  I tried running R3.14.11, but there are some incompatibilities noticed, so I'm sticking with R3.14.8.2 for now.

Dave


Replies:
Re: help with StreamDevice Eric Norum

Navigate by Date:
Prev: Re: Problem in errlogRemoveListener Benjamin Franksen
Next: Re: help with StreamDevice Eric Norum
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: cannot start test application Costello, Charles C.
Next: Re: help with StreamDevice Eric Norum
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 20 Apr 2015 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·