Hi Kay:
Thank you for your response and important information.
We hope that we will update the control software from EPICS V3.13 to EPICS V3.14 in short time, especially keeping the existing the architecture of ControlLogix hardware.
we perfer finding or converting driver of ControlNet interface module from V3.13 to V3.14, if there is no critical failure about ControlNet interface module.
Of course, the Ethernet-based EPICS interface for A/B ControlLogix PLC will be second alternative.
Best regards,
Gang
> -----原始邮件-----
> 发件人: "Kasemir, Kay" <[email protected]>
> 发送时间: 2018-01-24 22:10:03 (星期三)
> 收件人: "李刚" <[email protected]>, "[email protected]" <[email protected]>
> 抄送:
> 主题: Re: Driver support of VMM ControlNet interface module (5136-CN-VME)
>
> Hi:
>
> At the time, SNS evaluated integrating Control Logix PLC in two ways:
> 1) Via a VME ControlNet interface module and the driver that you describe
> 2) Via Ethernet, see "A/B Logix 5000 series of PLCs" on the EPICS driver list, https://epics.anl.gov/modules/bus.php#Ethernet;
>
> We decided to go with Ethernet, because it does not require a special VME module. IOCs can be vxWorks, Linux, .. In addition, the ethernet-based driver can read & write any controller tags on the PLC, no need to schedule control net traffic.
> As a result, I don't think the original VME ControlNet support for the 5136-CN-VME has been maintained.
> To access the Control Logix PLC via the ethernet-based EPICS interface, the PLC obviously needs an ethernet connection.
> For older Control Logix PLCs this means you add an ENET module to the PLC.
> The recent models have an ethernet connector on the controller/CPU.
>
> -Kay
>
>
>
>
>
>
> From: [email protected] <[email protected]> on behalf of 李刚 <[email protected]>
> Sent: Wednesday, January 24, 2018 3:30 AM
> To: [email protected]
> Subject: Driver support of VMM ControlNet interface module (5136-CN-VME)
>
> Hi all,We built the BEPC cryogenic and vacuum control system, using ControlLogix PLC via Controlnet module (EPICS driver originally developed by SNS of USA), based on EPICS Base R3.13(VME_IOC), about ten years ago, at IHEP of China.
>
>
> Now, we want to update the control software from Base R3.13 to Base R3.14 with keeping the existing hardware. However, I could't find any information about EPICS Base R3.14 VxWorks driver of VME ControlNet interface module(5136-CN-VME) from the website https://epics.anl.gov/modules/bus.php#VME%2dControlNet or https://ics-web.sns.ornl.gov/.
> Has anyone converted VME ControlNet driver from R3.13 to R3.14? or knows the status of VME ControlNet driver support? Any advice or suggest is appreciated. Best regardsGang
- References:
- Driver support of VMM ControlNet interface module (5136-CN-VME) 李刚
- Re: Driver support of VMM ControlNet interface module (5136-CN-VME) Kasemir, Kay
- Navigate by Date:
- Prev:
Re: Re: Question about communications based on modbus tcp. Mark Rivers
- Next:
答复: Re: Question about communications based on modbus tcp. lzf neu
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
<2018>
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: Driver support of VMM ControlNet interface module (5136-CN-VME) Kasemir, Kay
- Next:
Career Opportunity White, Karen S.
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
<2018>
2019
2020
2021
2022
2023
2024
|