1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  <20232024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  <20232024 
<== Date ==> <== Thread ==>

Subject: Re: modbus ioc start
From: Dale Cox via Tech-talk <tech-talk at aps.anl.gov>
To: Mark Rivers <rivers at cars.uchicago.edu>
Cc: "tech-talk at aps.anl.gov" <tech-talk at aps.anl.gov>
Date: Mon, 17 Apr 2023 08:22:43 -0500
Here is the dbpr of the longout for the whole register:

epics> dbpr DALE:Z8TC:Z8TC1-Conf1_debug 2    
ACKS: NO_ALARM      ACKT: YES           ADEL: 0             AMSG:              
ASG :               BKPT: 00            DESC:               DISA: 0            
DISP: 0             DISS: NO_ALARM      DISV: 1             DOL : CONSTANT      
DRVH: 0             DRVL: 0             DTYP: asynUInt32Digital                
EGU :               EVNT:               FLNK: CONSTANT      HHSV: NO_ALARM      
HIGH: 0             HIHI: 0             HOPR: 0             HSV : NO_ALARM      
HYST: 0             IVOA: Continue normally                 IVOV: 0            
LCNT: 0             LLSV: NO_ALARM      LOLO: 0             LOPR: 0            
LOW : 0             LSV : NO_ALARM      MDEL: 0            
NAME: DALE:Z8TC:Z8TC1-Conf1_debug       NAMSG:              NSEV: NO_ALARM      
NSTA: NO_ALARM      OMSL: supervisory   OOCH: YES           OOPT: Every Time    
OUT : INST_IO @asynMask(Z8TC1_Config 0 0xFFFF)              PACT: 0            
PHAS: 0             PINI: NO            PRIO: LOW           PUTF: 0            
PVAL: 0             RPRO: 0             SCAN: Passive       SDIS: CONSTANT      
SDLY: -1            SEVR: INVALID       SIML: CONSTANT      SIMM: NO            
SIMS: NO_ALARM      SIOL: CONSTANT      SSCN: 65535         STAT: UDF          
TIME: <undefined>   TPRO: 0             TSE : 0             TSEL: CONSTANT      
UDF : 1             UDFS: INVALID       VAL : 0 

On Mon, Apr 17, 2023 at 8:20 AM Dale Cox <dale.cox at acu.edu> wrote:
Sorry about that.  Here you go

epics> dbpr DALE:Z8TC:Z8TC1-Conf-TC1_enable 2
ACKS: NO_ALARM      ACKT: YES           AMSG:               ASG :              
BKPT: 00            COSV: NO_ALARM      DESC:               DISA: 0            
DISP: 0             DISS: NO_ALARM      DISV: 1             DOL : CONSTANT      
DTYP: asynUInt32Digital                 EVNT:               FLNK: CONSTANT      
HIGH: 0             IVOA: Continue normally                 IVOV: 0            
LCNT: 0             MASK: 32768         NAME: DALE:Z8TC:Z8TC1-Conf-TC1_enable  
NAMSG:              NSEV: NO_ALARM      NSTA: NO_ALARM      OMSL: supervisory  
ONAM: Enabled       OSV : NO_ALARM      
OUT : INST_IO @asynMask(Z8TC1_Config, 0, 0x8000)            PACT: 0            
PHAS: 0             PINI: NO            PRIO: LOW           PUTF: 0            
RBV : 0             RPRO: 0             RVAL: 0             SCAN: Passive      
SDIS: CONSTANT      SDLY: -1            SEVR: INVALID       SIML: CONSTANT      
SIMM: NO            SIMS: NO_ALARM      SIOL: CONSTANT      SSCN: 65535        
STAT: UDF           TIME: <undefined>   TPRO: 0             TSE : 0            
TSEL: CONSTANT      UDF : 1             UDFS: INVALID       VAL : 0            
ZNAM: Disabled      ZSV : NO_ALARM

 epics> dbpr DALE:Z8TC:Z8TC1-Conf-TC2_enable 2            
ACKS: NO_ALARM      ACKT: YES           AMSG:               ASG :              
BKPT: 00            COSV: NO_ALARM      DESC:               DISA: 0            
DISP: 0             DISS: NO_ALARM      DISV: 1             DOL : CONSTANT      
DTYP: asynUInt32Digital                 EVNT:               FLNK: CONSTANT      
HIGH: 0             IVOA: Continue normally                 IVOV: 0            
LCNT: 0             MASK: 16384         NAME: DALE:Z8TC:Z8TC1-Conf-TC2_enable  
NAMSG:              NSEV: NO_ALARM      NSTA: NO_ALARM      OMSL: supervisory  
ONAM: Enabled       OSV : NO_ALARM      
OUT : INST_IO @asynMask(Z8TC1_Config, 0, 0x4000)MODBUS_DATA PACT: 0            
PHAS: 0             PINI: NO            PRIO: LOW           PUTF: 0            
RBV : 0             RPRO: 0             RVAL: 0             SCAN: Passive      
SDIS: CONSTANT      SDLY: -1            SEVR: INVALID       SIML: CONSTANT      
SIMM: NO            SIMS: NO_ALARM      SIOL: CONSTANT      SSCN: 65535        
STAT: UDF           TIME: <undefined>   TPRO: 0             TSE : 0            
TSEL: CONSTANT      UDF : 1             UDFS: INVALID       VAL : 0            
ZNAM: Disabled      ZSV : NO_ALARM

 epics> dbpr DALE:Z8TC:Z8TC1-Conf-TC1-2_units 2
ACKS: NO_ALARM      ACKT: YES           AMSG:               ASG :              
BKPT: 00            COSV: NO_ALARM      DESC:               DISA: 0            
DISP: 0             DISS: NO_ALARM      DISV: 1             DOL : CONSTANT      
DTYP: asynUInt32Digital                 EVNT:               FLNK: CONSTANT      
HIGH: 0             IVOA: Continue normally                 IVOV: 0            
LCNT: 0             MASK: 8192          NAME: DALE:Z8TC:Z8TC1-Conf-TC1-2_units  
NAMSG:              NSEV: NO_ALARM      NSTA: NO_ALARM      OMSL: supervisory  
ONAM: mV            OSV : NO_ALARM      
OUT : INST_IO @asynMask(Z8TC1_Config, 0, 0x2000)MODBUS_DATA PACT: 0            
PHAS: 0             PINI: NO            PRIO: LOW           PUTF: 0            
RBV : 0             RPRO: 0             RVAL: 0             SCAN: Passive      
SDIS: CONSTANT      SDLY: -1            SEVR: INVALID       SIML: CONSTANT      
SIMM: NO            SIMS: NO_ALARM      SIOL: CONSTANT      SSCN: 65535        
STAT: UDF           TIME: <undefined>   TPRO: 0             TSE : 0            
TSEL: CONSTANT      UDF : 1             UDFS: INVALID       VAL : 0            
ZNAM: tempDegC      ZSV : NO_ALARM 

On Mon, Apr 17, 2023 at 8:13 AM Mark Rivers <rivers at cars.uchicago.edu> wrote:
Hi Dale,

You forgot to put the "2" at the end of the dbpr commands.  That will print more information.  Please do again with the final 2.

I see that RVAL is 0 for all 3 records.  That is not what it should be, since we think a non-zero value was read back from the driver in init_record.

Mark



From: Dale Cox <dale.cox at acu.edu>
Sent: Monday, April 17, 2023 8:06 AM
To: Mark Rivers <rivers at cars.uchicago.edu>
Cc: tech-talk at aps.anl.gov <tech-talk at aps.anl.gov>
Subject: Re: modbus ioc start
 
Mark, Here are the following returns for dbpr of those db records:

epics> dbpr DALE:Z8TC:Z8TC1-Conf-TC1_enable
AMSG:               ASG :               DESC:               DISA: 0            
DISV: 1             NAME: DALE:Z8TC:Z8TC1-Conf-TC1_enable   NAMSG:              
RBV : 0             RVAL: 0             SEVR: INVALID       STAT: UDF          
TPRO: 0             VAL : 0

 epics> dbpr DALE:Z8TC:Z8TC1-Conf-TC2_enable
AMSG:               ASG :               DESC:               DISA: 0            
DISV: 1             NAME: DALE:Z8TC:Z8TC1-Conf-TC2_enable   NAMSG:              
RBV : 0             RVAL: 0             SEVR: INVALID       STAT: UDF          
TPRO: 0             VAL : 0 

 epics> dbpr DALE:Z8TC:Z8TC1-Conf-TC1-2_units
AMSG:               ASG :               DESC:               DISA: 0            
DISV: 1             NAME: DALE:Z8TC:Z8TC1-Conf-TC1-2_units  NAMSG:              
RBV : 0             RVAL: 0             SEVR: INVALID       STAT: UDF          
TPRO: 0             VAL : 0 

I'm creating the longout record now. I'll post it's readouts in a bit. 

On Sat, Apr 15, 2023 at 8:24 AM Mark Rivers <rivers at cars.uchicago.edu> wrote:
Hi Dale,

> Is it supposed to say "asynSuccess" at the end of the highlighted section?  I get a "return 0".

Yes, asynSuccess is an enum with the value 0.

Mark



From: Dale Cox <dale.cox at acu.edu>
Sent: Friday, April 14, 2023 8:43 AM
To: Mark Rivers <rivers at cars.uchicago.edu>
Cc: tech-talk at aps.anl.gov <tech-talk at aps.anl.gov>
Subject: Re: modbus ioc start
 
Thanks for the reply Mark.

(1) Yes I thought this was the case.  Whenever I enable some asyn trace lines in the IOC, I can see the initial modbus request. It looks like this:

...
drvModbusAsynConfigure("Z8TC1_Config", "SenecaBus", 5, 6, 53, 4, "UINT16", 400, "SenecaZ")
2023/04/14 08:32:01.482 SenecaBus asynManager::queueLockPort locking port
2023/04/14 08:32:01.482 SenecaBus asynManager::queueLockPort created queueLockPortPvt=0x55ec3aba5df0
2023/04/14 08:32:01.482 SenecaBus asynManager::queueLockPort created queueLockPortPvt=0x55ec3aba5df0, event=0x55ec3aba5e10, mutex=0x55ec3aba5eb0
2023/04/14 08:32:01.482 SenecaBus asynManager::queueLockPort taking mutex 0x55ec3aba5eb0
2023/04/14 08:32:01.482 SenecaBus asynManager::queueLockPort queueing request
2023/04/14 08:32:01.482 SenecaBus addr -1 queueRequest priority 0 not lockHolder
2023/04/14 08:32:01.482 SenecaBus schedule queueRequest timeout in 2.000000 seconds
2023/04/14 08:32:01.482 SenecaBus asynManager::queueLockPort waiting for event
2023/04/14 08:32:01.482 asynManager::portThread port=SenecaBus callback
2023/04/14 08:32:01.482 SenecaBus asynManager::queueLockPortCallback signaling begin event
2023/04/14 08:32:01.482 SenecaBus asynManager::queueLockPortCallback waiting for mutex from queueUnlockPort
2023/04/14 08:32:01.482 SenecaBus asynManager::queueLockPort got event from callback
2023/04/14 08:32:01.482 SenecaBus flush
2023/04/14 08:32:01.482 /dev/ttyUSB0 flush
2023/04/14 08:32:01.487 /dev/ttyUSB0 write.
2023/04/14 08:32:01.487 /dev/ttyUSB0 write 8

05 03 00 35 00 04 55 83
2023/04/14 08:32:01.487 wrote 8 to /dev/ttyUSB0, return asynSuccess
2023/04/14 08:32:01.487 asynOctetSyncIO wrote:

05 03 00 35 00 04
2023/04/14 08:32:01.487 /dev/ttyUSB0 read.
2023/04/14 08:32:01.495 /dev/ttyUSB0 read 13

05 03 08 d0 11 d2 00 d2 00 d2 11 3b 1c
2023/04/14 08:32:01.495 /dev/ttyUSB0 read 13, return 0
2023/04/14 08:32:01.495 SenecaBus read 13 bytes eom=0


05 03 08 d0 11 d2 00 d2 00 d2 11 3b 1c
2023/04/14 08:32:01.495 asynOctetSyncIO read:

03 08 d0 11 d2 00 d2 00 d2 11
2023/04/14 08:32:01.495 SenecaBus queueUnlockPort
2023/04/14 08:32:01.495 SenecaBus asynManager::queueUnlockPort waiting for event
2023/04/14 08:32:01.495 SenecaBus queueUnlockPort unlock mutex 0x55ec3aba5eb0 complete.
...

So I'm getting the requested registers back on that port, and you can see their values there.  d0 11 is 1101000000010001 in binary, so when I look at the 15th bit, it should return back a 1.  when I do a caget on that PV, I get a 0 (I get 0's for all of the records associated with these registers).

Is it supposed to say "asynSuccess" at the end of the highlighted section?  I get a "return 0".


Thanks for helping me troubleshoot.

Dale


On Thu, Apr 13, 2023 at 4:38 PM Mark Rivers <rivers at cars.uchicago.edu> wrote:

Hi Dale,

 

  • My issue is that the PV values aren't being updated when the IOC starts -- meaning that after the IOC start, the bo and mbbo values stored in that register don't match what was returned via the initial modbus request.

 

I am not sure I completely understand what you are saying.  Here is what should happen:

 

  1. Because this port you created uses function code 6 (write single register) and because you have a non-zero poll time, the driver will do one initial read of that register using function code 3.
  2. EPICS device support for the bo records does a read operation from the port during init_record.  If this read returns asynSuccess (which it should) then the value of the bo record is set to the value read from the driver.  This is the “bumpless reboot” concept.
  3. You have not set PINI=YES in these records, so the value from the record will not be written back to the device during iocInit.  However, the record value should still match the device, because of steps 1 and 2 above.

 

If I understand correctly you are saying that the bo record does have the correct value read from the device during steps 1-2.  But now the device has a different value from that in the record?  I don’t understand that, since it seems like there must have been a write to the device to change the value?

 

Mark

 

 

From: Tech-talk <tech-talk-bounces at aps.anl.gov> On Behalf Of Dale Cox via Tech-talk
Sent: Thursday, April 13, 2023 8:29 AM
To: tech-talk at aps.anl.gov
Subject: modbus ioc start

 

Good Morning,

 

I have an IOC that is currently reading registers via modbus rtu over rs485.  There are a set of registers that store multiple configuration options in a single register.  I set up the port using this line:

 

> drvModbusAsynConfigure("Z8TC1_Config", "SenecaBus", 5, 6, 53, 4, "UINT16", 100, "SenecaZ")

 

I've enabled the debugging lines on this IOC. When the IOC starts, I can see that the correct registers are being retrieved when the port is created.  I can also write config changes to those registers at their assigned PV's with no issues that I have found.  My issue is that the PV values aren't being updated when the IOC starts -- meaning that after the IOC start, the bo and mbbo values stored in that register don't match what was returned via the initial modbus request.

 

Here are a couple of the DB entries that I'm using:

 

record(bo,"$(P)$(R)-TC1_enable") {
    field(DTYP,"asynUInt32Digital")
    field(OUT,"@asynMask($(PORT), 0, 0x8000 )")
    field(ZNAM,"Disabled")
    field(ONAM,"Enabled")
}

record(bo,"$(P)$(R)-TC2_enable") {
    field(DTYP,"asynUInt32Digital")
    field(OUT,"@asynMask($(PORT), 0, 0x4000 )")
    field(ZNAM,"Disabled")
    field(ONAM,"Enabled")
}

record(bo,"$(P)$(R)-TC1-2_units") {
    field(DTYP,"asynUInt32Digital")
    field(OUT,"@asynMask($(PORT), 0, 0x2000 )")
    field(ZNAM,"tempDegC")
    field(ONAM,"mV")
}

 

Any help is appreciated.

 

Dale 

 

--

Dale Cox

Instrumentation and Electrical Engineer

ACU NEXT Lab 


References:
modbus ioc start Dale Cox via Tech-talk
RE: modbus ioc start Mark Rivers via Tech-talk
Re: modbus ioc start Dale Cox via Tech-talk
Re: modbus ioc start Mark Rivers via Tech-talk
Re: modbus ioc start Dale Cox via Tech-talk
Re: modbus ioc start Mark Rivers via Tech-talk
Re: modbus ioc start Dale Cox via Tech-talk

Navigate by Date:
Prev: Re: modbus ioc start Dale Cox via Tech-talk
Next: Re: modbus ioc start Torsten Bögershausen via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  <20232024 
Navigate by Thread:
Prev: Re: modbus ioc start Dale Cox via Tech-talk
Next: Re: modbus ioc start Torsten Bögershausen via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  <20232024 
ANJ, 17 Apr 2023 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·