Subject: |
Re: pvget to an _output_ record |
From: |
[email protected] (Marty Kraimer) |
Date: |
Tue, 6 Dec 1994 07:52:15 -0600 |
> >
> > I see that the record structures include entries for things like:
> > long rbv; /* Readback Value */
> > long orbv; /* Prev Readback Value */
> > etc
> >
> > but it's not clear how these values get set and who uses them. Or even if
> > they are applicable to the problem.
The fields (rbv,orbv) and (rval,oraw) are used to keep track of the readback
values from the device (Nice devices provide this capability. Many devices
are not nice). (rval,oraw) are the raw values and (rbv,orbv) the values in eng
units. orbv and oraw are used to decide if monitors should be raised for
rbv and rval.
Marty Kraimer