Subject: |
Xy220 device bug ? |
From: |
[email protected] (Chris Mayer) |
Date: |
Mon, 19 Dec 94 15:11:43 GMT |
We have been trying to use the Xy220 via a mbbo and found that we could not
drive the outputs that we wanted. Looking at the device layer code it seems
there is a missing shift operator in the init_record procedure i.e.
pmbbo->mask = pmbbo->shft
should read
pmbbo->mask <<= pmbbo->shft
has anyone else come across this problem and / or is this the correct way to
fix it ? We are running r3.11.4 epics but looking in the beta release of r3.12
that we have appears to show the same problem.
Chris Mayer
RGO
- Navigate by Date:
- Prev:
Installation Guide needs Vladimir Romanovski
- Next:
Re: Xy220 device bug ? Marty Kraimer
- Index: