Paul Sichta wrote:
>
> I am using gdct313 to define an MBBI record and there is no place on the
> "Edit Attributes" form for specifying the number of bits to 'shift' the raw
> value (SHFT). mbbiRecord.dbd does not assign the SHFT field to a
> promptgroup. Is there a reason for this omission ?
The SHFT field is filled in by the device support layer automatically.
In your database you should just set the INP field to give the Card and
Signal number (or whatever address specification is used by your
particular device) of the lowest bit used, and set NOBT to the number of
bits to read. The same applies to the other binary record types.
-- Andrew
___
.' `. Andrew Johnson, Head of Electronics
/ Royal ) Royal Greenwich Observatory
\ Greenwich Madingley Road, Cambridge, CB3 0EZ
| Observatory Tel: +44 1223 374823 Fax: 374700
+---------- WWW: http://www.ast.cam.ac.uk/~anj
- References:
- MBBI, SHFT, and GDCT Paul Sichta
- Navigate by Date:
- Prev:
MBBI, SHFT, and GDCT Paul Sichta
- Next:
Re: MBBI, SHFT, and GDCT Ralph Lange
- Index:
1994
1995
1996
1997
<1998>
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
MBBI, SHFT, and GDCT Paul Sichta
- Next:
Re: MBBI, SHFT, and GDCT Ralph Lange
- Index:
1994
1995
1996
1997
<1998>
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
|
ANJ, 10 Aug 2010 |
·
Home
·
News
·
About
·
Base
·
Modules
·
Extensions
·
Distributions
·
Download
·
·
Search
·
EPICS V4
·
IRMIS
·
Talk
·
Bugs
·
Documents
·
Links
·
Licensing
·
|