On Monday, March 08, 1999 10:25 AM, John A. Priller [SMTP:[email protected]] wrote:
> I don't have an answer to that (sorry), but I'd like to add a somewhat
> related question to the discussion: I'm using the portable Channel Access
> Server on Windows NT PCs to add our Modicon/PLC information into the EPICS
> system. I have two server PCs, for redundancy, and whenever I launch MEDM
> or Probe for one of these channels I get the same error message Natalie is
> getting. Is there any way of turning this off?
>
Sorry, you can not have the same PV name in two different CA servers on the same subnet
in the current and past versions of EPICS unless each of the servers involved is configured
to use different port numbers.
It is also currently not recommended to run two ca servers on the same host with the same port
number.