1994  1995  1996  1997  1998  1999  <20002001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  <20002001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Hardware to for thermocouple readout
From: Steve Lewis <[email protected]>
To: "Porter, Rodney" <[email protected]>
Cc: [email protected]
Date: Wed, 26 Apr 2000 08:58:01 -0700
At 5:24 PM -0500 2000/04/25, Porter, Rodney wrote:
>I need to monitor 24 thermocouples.  Can someone suggest EPICS supported
>hardware for this application.  


Our method of choice here is to hook them directly to Allen-Bradley
Flex-I/O modules which are deployed close to the sensors.  These 8-channel
units handle all known types, and have cold-junction compensation
and a calibration procedure.  The unit is model IT-8.

Three IT-8 units can be combined in a small DIN-rail stack. (And they can
be mixed with other units for handling pressure, flow, whatever, in a nicely
distributed manner.)  With adaptor and power supply (but not including
6008 scanner) using typical discounts, it would cost about $3700

They can connect to the IOC either directly to the 6008 scanner (we are
just finishing device support) or via any A-B series PLC (in which case
the generic PLC device support already works).

We much prefer this "raw sensor" approach here to the rack-mounted/
multiplexed/bells-and-whistles/RS-485-protocol-from-hell style of the
typical catalog instrument.  Your mileage may vary...

_____________________________________________________________________
Stephen A. Lewis                        | [email protected]
Mail Stop 71-259                        | http://www.lbl.gov/~salewis
Lawrence Berkeley National Laboratory   | Tel: +1.510.486.7702
Berkeley, CA 94720    USA               | FAX: +1.510.486.4544


Replies:
Re: Hardware to for thermocouple readout Steve Hunt
References:
Hardware to for thermocouple readout Porter, Rodney

Navigate by Date:
Prev: Re: Hardware to for thermocouple readout Marty Kraimer
Next: Re: Hardware to for thermocouple readout Steve Hunt
Index: 1994  1995  1996  1997  1998  1999  <20002001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Hardware to for thermocouple readout Marty Kraimer
Next: Re: Hardware to for thermocouple readout Steve Hunt
Index: 1994  1995  1996  1997  1998  1999  <20002001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 10 Aug 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·