1994  1995  1996  1997  1998  1999  <20002001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  <20002001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Hardware to for thermocouple readout
From: Steve Lewis <[email protected]>
To: Steve Hunt <[email protected]>
Cc: [email protected]
Date: Thu, 27 Apr 2000 09:13:40 -0700
At 8:30 AM +0200 2000/04/27, Steve Hunt wrote:
>Would anyone be willing to  comment on the accuracy and resolution achieved with
>these different solutions proposed  for thermocouple measurements ?


The Allen-Bradley 1794-IT8 provides 0.1 resolution in deg C or deg F.
(It also can act as a calibrated pre-amp to any millivolt source.)
Fundamental digitizer provides 16 bits.  However, you can trade-off
scan time for resolution: 8 channels scanned at 16 bits takes 2 seconds
down to 9 bits taking 50 milliseconds.

_____________________________________________________________________
Stephen A. Lewis                        | [email protected]
Mail Stop 71-259                        | http://www.lbl.gov/~salewis
Lawrence Berkeley National Laboratory   | Tel: +1.510.486.7702
Berkeley, CA 94720    USA               | FAX: +1.510.486.4544


References:
Hardware to for thermocouple readout Porter, Rodney
Re: Hardware to for thermocouple readout Steve Lewis
Re: Hardware to for thermocouple readout Steve Hunt

Navigate by Date:
Prev: Re: Hardware to for thermocouple readout Marty Kraimer
Next: Fast Ethernet and Baja Alastair Borrowman
Index: 1994  1995  1996  1997  1998  1999  <20002001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Hardware to for thermocouple readout Marty Kraimer
Next: RE: Hardware to for thermocouple readout Mark Rivers
Index: 1994  1995  1996  1997  1998  1999  <20002001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 10 Aug 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·