1994  1995  1996  1997  1998  1999  <20002001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  <20002001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: ca error
From: Matthieu Bec <[email protected]>
To: <[email protected]>
Date: Fri, 22 Sep 2000 08:01:28 -1000 (HST)
Hi GongFa,

The message indicates too many open files. Why would that happen is 
not clear, we don't use iocLogClient on our ioc (!)
Try login on your console and type 'iosFdShow'.
It depend on what you'd expect, but you always could increase the 
default value (50) by recompiling VxWorks, there's an entry 
NUM_FILES in your config.h that set the maximum.

hope that helps,
Matthieu


Matthieu Bec              Gemini Observatory
Tel: +1 808 9742557       670 N. A'ohoku Place
Fax: +1 808 9359235       Hilo, Hawaii 96720, USA


Replies:
Re: ca error Dale L. Brewe
References:
ca error GongFa Liu

Navigate by Date:
Prev: ca error GongFa Liu
Next: Re: ca error Dale L. Brewe
Index: 1994  1995  1996  1997  1998  1999  <20002001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: ca error GongFa Liu
Next: Re: ca error Dale L. Brewe
Index: 1994  1995  1996  1997  1998  1999  <20002001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 10 Aug 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·