Hi all,
just went through a bit of confusion with the alarm handler and
thought I'd pass it on:
once we got the first one working I copied alarm handler config
files and edited them by hand (for a few years now). As we just got
a new instrument we wanted to set up alarms (email by list-forwarding)
for this one too and I set up the limits, etc. as well as the
config files.
For some reason which escaped me the mail didn't work, the address list
got cut off somewhere by something (there are several solaris machines
involved, and a somewhat complicated system of centralized mail
forwarding).
It appears that the cut-off in the addressing is not in the mail
forwarding but in the alarm handler reading its configuration file.
What is the limit on the line length in alarm handler config files?
The problem in finding this was of course that all stages of the
forwarding start with the same 5 characters - my user ID.
Aloha,
Maren
- Replies:
- Re: alarm handler confusion (and solution) Ralph . Lange
- Navigate by Date:
- Prev:
RE: bug report Jeff Hill
- Next:
Re: alarm handler confusion (and solution) Ralph . Lange
- Index:
1994
1995
1996
1997
1998
1999
2000
<2001>
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
RE: bug report Jeff Hill
- Next:
Re: alarm handler confusion (and solution) Ralph . Lange
- Index:
1994
1995
1996
1997
1998
1999
2000
<2001>
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
|