David Dudley wrote: I have a BO where every time I trigger it, I want to output a constant value. Since the .VAL field can't be set to a constant through vdct, is there an easy way to force it to have a '1' value all the time? Set the DOL field to the value you want, and the OMSL field to "closed_loop". But I'm surprised that you can't set the VAL field using vdct. I can, with EPICS 3.14.8.2. (I think vdct will let you set a field if the .dbd file specifies a promptgroup for the field. I'm using vdct 2.5, build 1271, by the way.) -- Tim Mooney ([email protected]) (630)252-5417 Beamline Controls & Data Acquisition Group Advanced Photon Source, Argonne National Lab.
| ||||||||||||||||