1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  <20082009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  <20082009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: EPICS and CAN field bus
From: Graham Waters <[email protected]>
To: Ralph Lange <[email protected]>
Cc: EPICS Tech Talk <[email protected]>
Date: Mon, 20 Oct 2008 13:26:30 -0700
Its still at a development stage but as part of our move to linux I have a driver for the TEWS TPMC810 CANbus interface.
We run linux on a GMS Condor which is a VME Single Board Computer with one onboard PMC slot.


The Linux device driver is available from TEWS technologies
The EPIC driver support software is adapted from a vxWorks driver for the TIP810 (industry pack) by Andrew Johnson
For use in a PC, TEWS have a PMC to PCI adapter (TPC1270)


Graham

Ralph Lange wrote:
Hi all,

is anyone out there connecting from EPICS to CAN field bus using an IOC on PC hardware?
What CAN interface hardware do you use? What OS is this running on? (Linux preferred...)


What's the status of Marty's IP/PCI driver for Linux? (Still listed as 1.0alpha0 on the EPICS web.)
Would you consider putting a Tews TIP810 on such a carrier board to be a good idea?


Thanks for your help!
Ralph




--
+---------------------------------------------------------------------+
|Graham Waters, Control System Eng phone: (604)-222-1047 ext 6531 |
|TRIUMF --- University of B.C, Fax: (604)-222-7307 |
|Vancouver, BC, Canada e-mail: [email protected] |
| |
|http://isacwserv.triumf.ca/edevel/homepage/graham01.html |
+---------------------------------------------------------------------+




References:
EPICS and CAN field bus Ralph Lange

Navigate by Date:
Prev: RE: Inter-IOC link problems Jeff Hill
Next: Difficulties with my Sequencer program Szalata, Zenon M.
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  <20082009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: EPICS and CAN field bus Marty Kraimer
Next: RE: EPICS and CAN field bus David Beauregard
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  <20082009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 02 Sep 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·