If it helps, this IOC has 2 stuck sequences:
#1 of 1:
Channel name: "R35"
Unexpanded (assigned) name: "{pv}"
Variable name: "VAL"
address = 145117704 = 0x8a65208
type = int
count = 1
Value = 0
Monitor flag = 1
Monitored
Assigned
Connected
Get not completed or no get issued
Put not completed or no put issued
Status = 0
Severity = 0
Message =
Time stamp = <undefined>
Next? (+/- skip count)
sioc-sys0-ss00>
[detached]
Connection to lcls-dev2 closed.
lcls-zelazny bash:/nfs/slac/g/lcls/epics/ioc/data/sioc-sys0-ss00>caget R35
R35 70
lcls-zelazny bash:/nfs/slac/g/lcls/epics/ioc/data/sioc-sys0-ss00>
________________________________________
From: [email protected] [[email protected]] On Behalf Of Zelazny, Michael Stanley [[email protected]]
Sent: Monday, September 26, 2011 5:22 PM
To: [email protected]; Shankar, Murali; Zhou, Jingchen; Williams Jr., Ernest L.
Subject: RE: Sequence monitor not getting callback
Murali,
Here is the error. Please debug and fix if you can.
Thanks,
Mike
#1 of 1:
Channel name: "J60"
Unexpanded (assigned) name: "{pv}"
Variable name: "VAL"
address = 2716111720 = 0xa1e49368
type = int
count = 1
Value = 0
Monitor flag = 1
Monitored
Assigned
Connected
Get not completed or no get issued
Put not completed or no put issued
Status = 0
Severity = 0
Message =
Time stamp = <undefined>
Next? (+/- skip count)
sioc-sys0-ss00>
[detached]
Connection to lcls-dev2 closed.
lcls-zelazny bash:/nfs/slac/g/lcls/epics/ioc/data/sioc-sys0-ss00>caget J60
J60 17
lcls-zelazny bash:/nfs/slac/g/lcls/epics/ioc/data/sioc-sys0-ss00>
________________________________________
From: [email protected] [[email protected]] On Behalf Of Zelazny, Michael Stanley [[email protected]]
Sent: Monday, September 26, 2011 3:02 PM
To: [email protected]; Shankar, Murali; Zhou, Jingchen; Williams Jr., Ernest L.
Subject: RE: Sequence monitor not getting callback
Ben, Murali,
Any idea what the "numMonitoredChans 1 firstMonitorCount 0 assignCount 1 firstConnectCount 1" message is trying to tell me?
[snip]
# Set ioc console prompt
epicsEnvSet("IOCSH_PS1","sioc-sys0-ss00>")
# Post Startup Complete, the IRMIS crawler appreciates your cooperation.
sioc-sys0-ss00>numMonitoredChans 1 firstMonitorCount 0 assignCount 1 firstConnectCount 1
sioc-sys0-ss00>seqcar
Total programs=2600, channels=2600, connected=2600, disconnected=0
sioc-sys0-ss00>numMonitoredChans 1 firstMonitorCount 0 assignCount 1 firstConnectCount 1
numMonitoredChans 1 firstMonitorCount 0 assignCount 1 firstConnectCount 1
sioc-sys0-ss00>
sioc-sys0-ss00>
sioc-sys0-ss00>
sioc-sys0-ss00>
[snip]
Background:
I'm trying to reproduce the "sequence not getting its monitor callback" problem.
I have 2600 sequences running:
lcls-zelazny bash:~/epics/ioc/SeqSupport/SeqSupportApp/src>cat SeqChecker.st
program SeqChecker
%%#include <string.h> /* sprintf prototype */
%%#include <errlog.h> /* errlogPrintf */
option +c; /* All connections must be made before execution begins */
option +d; /* Turn on runtime debug messages */
option +r; /* All declarations private to this sequence */
option -a; /* All pvGets must be synchronous */
int VAL;
assign VAL to "{pv}";
monitor VAL;
ss SeqCheckerss {
state checking {
when (0 == VAL) {
errlogPrintf("%s failed to get its monitor.\n");
epicsThreadSleep(60);
} state checking
}
}
lcls-zelazny bash:~/epics/ioc/SeqSupport/SeqSupportApp/src>
The pv's are:
lcls-zelazny bash:~/epics/ioc/SeqSupport/SeqSupportApp/Db>cat SeqSupport.vdb
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/SeqSupport.dbd")
#! DBDEND
record(calc, "${pv}") {
field(SCAN, "10 second")
field(PINI, "YES")
field(VAL, "1")
field(CALC, "A + 1")
field(INPA, "${pv}")
}
#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("${pv}",2300,2254,0,1,"${pv}")
#! Field("${pv}.VAL",16777215,0,"${pv}.VAL")
#! Field("${pv}.INPA",16777215,0,"${pv}.INPA")
#! Link("${pv}.INPA","${pv}.VAL")
lcls-zelazny bash:~/epics/ioc/SeqSupport/SeqSupportApp/Db>
- References:
- Sequence monitor not getting callback Zelazny, Michael Stanley
- Re: Sequence monitor not getting callback Benjamin Franksen
- RE: Sequence monitor not getting callback Zelazny, Michael Stanley
- RE: Sequence monitor not getting callback Zelazny, Michael Stanley
- Navigate by Date:
- Prev:
RE: Sequence monitor not getting callback Zelazny, Michael Stanley
- Next:
[S7plc EPICS driver] REAL type record jumps to zero Pavel Masloff
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
<2011>
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
RE: Sequence monitor not getting callback Zelazny, Michael Stanley
- Next:
Re: Sequence monitor not getting callback Benjamin Franksen
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
<2011>
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
|