1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019 
<== Date ==> <== Thread ==>

Subject: RE: TDS 3000 on win32-x86
From: Mark Rivers <rivers@cars.uchicago.edu>
To: Pavel Masloff <pavel.masloff@gmail.com>, EPICS Tech Talk <tech-talk@aps.anl.gov>, "Nicholas P. DiMonte" <npd@aps.anl.gov>
Date: Mon, 5 Mar 2012 14:38:23 +0000
Hi Pavel,

This error

ERROR: vxi11Configure is not supported on WIN32

is expected because there is no support for VXI-11 on win32-x86, because we don't have an implementation of Sun RPC for win32-x86, which the VXI-11 support requires.

However, this error:
drvAsynIPPortConfigure("L0", "172.20.92.3", 0, 0, 0)
st.cmd -- Line 50 -- Command drvAsynIPPortConfigure not found.

is not expected.  The drvAsynIPPortConfigure command works fine on win32-x86.  You must have a mistake in building your application, perhaps you forgot to include "drvAsynIPPort.dbd" in your dbd file.

Mark



________________________________
From: tech-talk-bounces@aps.anl.gov [tech-talk-bounces@aps.anl.gov] on behalf of Pavel Masloff [pavel.masloff@gmail.com]
Sent: Monday, March 05, 2012 8:31 AM
To: EPICS Tech Talk; Nicholas P. DiMonte
Subject: TDS 3000 on win32-x86

Hi Nick et al. :


I am trying to use your Tektronix TDS-3000 support on win32-x86. And I have found that it neither works via "Direct network connection" nor "GPIB/LAN connection":
ERROR: vxi11Configure is not supported on WIN32

Is there a possibility to talk to the TDS 3054C device any other way on win32? If so, could you give me a hint?
If using "Remote serial port", the following errors occur:
drvAsynIPPortConfigure("L0", "172.20.92.3", 0, 0, 0)
st.cmd -- Line 50 -- Command drvAsynIPPortConfigure not found.
asynOctetSetInputEos("L0",0,"\n")
Port L0 connectDevice failed: asynManager:connectDevice port L0 not found
asynOctetSetOutputEos("L0",0,"\n")
Port L0 connectDevice failed: asynManager:connectDevice port L0 not found


--
Best regards,


Pavel Maslov, MS
Controls Engineer at Pulsed power Lab
Efremov Institute for Electro-Physical Apparatus
St. Petersburg, Russia

Mobile: +7 (951) 672 22 19
Phone: +7 (812) 461 01 01


References:
TDS 3000 on win32-x86 Pavel Masloff

Navigate by Date:
Prev: TDS 3000 on win32-x86 Pavel Masloff
Next: Re: Problems with priorities in epicsThreadCreate: Thank you. Goetz Pfeiffer
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019 
Navigate by Thread:
Prev: TDS 3000 on win32-x86 Pavel Masloff
Next: TDS 3000 on win32-x86 Pavel Masloff
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  <20122013  2014  2015  2016  2017  2018  2019 
ANJ, 18 Nov 2013 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·