Yeah, you’re right because I just noticed that they have a 09000 address in there, so it’s definitely not octal.
Mark
From: Eric Norum [mailto:[email protected]]
Sent: Thursday, June 13, 2013 4:33 PM
To: Mark Rivers
Cc: EPICS Tech-Talk
Subject: Re: Horner PLC %T readout
No, I don't think that's the problem.
For the %R values the spreadsheet has values from R1100 through R1137. I can successfully read these using the command:
# Read 38 starting at Modbus 4099: Horner %R1100 through %R1137 inclusive
drvModbusAsynConfigure("etmHPA_r0i", "etmHPAPLC_2", 0, 3, 4099, 38, 0, 1000, "Horner")
So the values in the table shown in the right column of the table appear to be decimal.
In their table they list the Modbus offset for the %T1 register as 06000. I interpret that as octal 6000, because Modbus traditionally use octal, and they put a leading
0.
But in your drvModbusAsynConfigure command you did not put a leading 0, so it is interpreting it as decimal 6000.
Now you also need to figure out if T513 is 513 decimal from the beginning, or 513 octal!
|
- References:
- Horner PLC %T readout Eric Norum
- RE: Horner PLC %T readout Mark Rivers
- Re: Horner PLC %T readout Eric Norum
- Navigate by Date:
- Prev:
Re: Horner PLC %T readout Eric Norum
- Next:
Re: Adding error msgs to dbAccess.c Bruce Hill
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
<2013>
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: Horner PLC %T readout Eric Norum
- Next:
Looking for an network scope (with epics driver!) Emmanuel Mayssat
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
<2013>
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
|
ANJ, 20 Apr 2015 |
·
Home
·
News
·
About
·
Base
·
Modules
·
Extensions
·
Distributions
·
Download
·
·
Search
·
EPICS V4
·
IRMIS
·
Talk
·
Bugs
·
Documents
·
Links
·
Licensing
·
|