1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  <20162017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  <20162017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: MTCA4 HW management
From: Jeong Han Lee <[email protected]>
To: "Hill, Jeff" <[email protected]>
Cc: Han Lee <[email protected]>, "[email protected]" <[email protected]>
Date: Mon, 11 Jan 2016 19:29:55 +0100
Hi Jeff, Bob, Martin, and Sonya,

   Thank you for your comments, and support. All information should be
extreme useful  for me.  BYW, I cannot choose MTCA4, which was done
before I joined to ESS. My first concern is to make them (shelf, power
module, MicroTCA carrier Hub, cooling units) as stable (maybe my old
friend VME crate?) as possible under EPICS environment, because I feel
uncomfortable when I am close to look at the MTCA concept (I may be
too stupid to understand  the modern advanced technology).

  I am not sure I can achieve that goal, but I am sure I could do my
best as always I did.

  Thank you everyone again.

  Thanks,
  Han





On Mon, Jan 11, 2016 at 6:49 PM, Hill, Jeff <[email protected]> wrote:
> Han,
>
> FWIW, LANL decided to go with 3U VPX instead of uTCA. We created a chassis design enclosing a 6 slot 3u VPX backplane, a 6u Compact PCI backplane, and also four 3u Compact PCI modular redundant power supplies. The VPX hosts the COTS Altera DSP boards with FMC mezzanine modular COTS ADC, and the Compact PCI hosts the analog cards, general purpose IO, and MRF timing etc. We interconnect the two backplanes with PCIe over cable standard. We run EPICS on FPGA embedded nios2 soft-cores running RTEMS. We have a presentation at the last ICALEPCS.
>
> Jeff
>
>> -----Original Message-----
>> From: [email protected] [mailto:[email protected]]
>> On Behalf Of Sonya Hoobler
>> Sent: Monday, January 11, 2016 10:02 AM
>> To: [email protected]
>> Cc: Han Lee
>> Subject: Re: MTCA4 HW management
>>
>> Dear Han,
>>
>> In fact, SLAC does have a few MicroTCA systems. We did develop EPICS
>> monitoring for these systems, though it was never completed and still
>> contains some known bugs. This software discovers the shelf configuration
>> and monitors the shelf sensors.
>>
>> We plan to fix these early this year and to add support for some of our
>> other IPMI-based systems. We would be happy to share this code with you at
>> that time.
>>
>> Best regards,
>>    Sonya
>>
>> Sonya Hoobler
>> SLAC National Accelerator Laboratory
>> Instrumentation and Controls Division
>>
>>
>> >
>> > On Mon, Jan 11, 2016 at 4:42 AM, Jeong Han Lee <[email protected]>
>> > wrote:
>> >
>> >> Hi all,
>> >>
>> >>   I am looking for any existent EPICS support of MicroTCA HW management
>> or
>> >> any plan for that. I've heard that SLAC and DESY heavily (?) use that
>> >> platform so far, but there are no EPICS related activities I can find in
>> >> teck-talks and others.
>> >>
>> >>   Currently, my concern is to to maintain all MTCA4 HW (Chassis, Carrier
>> >> Hub, Backplane, Power Modules, Cooling Units, etc), because MTCA.4 HW is
>> >> still unstable (I mean comparing with any VME HW (I might be wrong) and
>> ESS
>> >> will use several hundred MicroTCA Chassis (crate).
>> >>
>> >> This maintenance has the following activities:
>> >>
>> >>   * monitor/change a status of MicroTCA HW though EPICS
>> >>   * update/revert the corresponding firmware through EPICS
>> >>   * all activities are recorded into a EPICS archive service (AA) (it is
>> >> clear evidence with EPICS)
>> >>
>> >>   So, we can scale this activities up to massive MicroTCA HW easily.
>> >>
>> >>   Please let me know if you know much better idea than my naive one, and
>> >> would you recommend what you're using?
>> >>
>> >>
>> >>   Thanks,
>> >>   Han
>> >>
>> >>
>> >>
>> >>
>> >>
>> >
>


References:
MTCA4 HW management Jeong Han Lee
Re: MTCA4 HW management bob dalesio
Re: MTCA4 HW management Sonya Hoobler
RE: MTCA4 HW management Hill, Jeff

Navigate by Date:
Prev: RE: MTCA4 HW management Hill, Jeff
Next: CAEN DT5730 support module? Ford, Christopher
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  <20162017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: RE: MTCA4 HW management Hill, Jeff
Next: Re: MTCA4 HW management Konrad, Martin
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  <20162017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 15 Jul 2016 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·