1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  <20162017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  <20162017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE: Long string command to device
From: <[email protected]>
To: <[email protected]>
Cc: [email protected]
Date: Tue, 20 Sep 2016 12:45:00 +0000
From: [email protected] [mailto:tech-talk-
> Thanks for the fast answer.
> Then the problem must be of a different kind (I am rather new to EPICS).
> 
> I have the following database records:
> 
> record(waveform, "$(P):RAW2") {
>    field(DTYP, "stream")
>    field(OUT, "@Huginn.proto setRAW $(PORT) $(ADDR)")
>    field(FTVL, "CHAR")
>    field(DESC, "RAW waveform lakeshore record")
>    field(SCAN, "Passive")
> }

The problem is simply that, quite confusingly, the control field in a waveform record is called INP, even if the device support is treating it as an out record.  Change OUT to INP and it might work

-- 
This e-mail and any attachments may contain confidential, copyright and or privileged material, and are for the use of the intended addressee only. If you are not the intended addressee or an authorised recipient of the addressee please notify us of receipt by returning the e-mail and do not use, copy, retain, distribute or disclose the information in or attached to the e-mail.
Any opinions expressed within this e-mail are those of the individual and not necessarily of Diamond Light Source Ltd. 
Diamond Light Source Ltd. cannot guarantee that this e-mail or any attachments are free from viruses and we cannot accept liability for any damage which you may sustain as a result of software viruses which may be transmitted in or with the message.
Diamond Light Source Limited (company no. 4375679). Registered in England and Wales with its registered office at Diamond House, Harwell Science and Innovation Campus, Didcot, Oxfordshire, OX11 0DE, United Kingdom



Replies:
Re: Long string command to device Pete Jemian
References:
Long string command to device Bo Jakobsen
RE: Long string command to device Mark Rivers
Re: Long string command to device Bo Jakobsen

Navigate by Date:
Prev: Re: Long string command to device Bo Jakobsen
Next: Ospreydcs.com bob dalesio
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  <20162017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Long string command to device Bo Jakobsen
Next: Re: Long string command to device Pete Jemian
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  <20162017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 20 Sep 2016 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·