EPICS Controls Argonne National Laboratory

Experimental Physics and
Industrial Control System

1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE: concurrent put callbacks
From: "Andrew C. Starritt" <[email protected]>
To: "Mooney, Tim M." <[email protected]>, "[email protected]" <[email protected]>
Date: Thu, 2 Nov 2017 21:46:40 +0000

Hi Tim,

 

I had a look at the sseq record and it is exactly the kind of thing I need – thanks.

 

Cheers

 

Andrew C. Starritt | Principal Controls Engineer | Australian Synchrotron
p: (03) 8540 4164 | f: (03) 8540 4200
[email protected] | www.synchrotron.org.au
800 Blackburn Road, Clayton, Victoria 3168

 

From: Mooney, Tim M. [mailto:[email protected]]
Sent: Friday, 3 November 2017 12:43 AM
To: Andrew C. Starritt; [email protected]
Subject: Re: concurrent put callbacks

 

The sseq record can do up to 10 actions in parallel, and then wait for all of them to complete.  Any set of consecutive output links can be done in parallel, and then waited for before going on to the next link.  The WAITn fields control this.  For example, to execute LNK2 and LNK3 in parallel, set WAIT2 to "After 3", and set WAIT3 to "Wait"

 

Tim Mooney ([email protected]) (630)252-5417
Beamline Controls Group (www.aps.anl.gov)
Advanced Photon Source, Argonne National Lab


From: [email protected] <[email protected]> on behalf of Andrew C. Starritt <[email protected]>
Sent: Thursday, November 2, 2017 2:24:23 AM
To: [email protected]
Subject: concurrent put callbacks

 

Hi al,

 

The sseq record is great for doing a number of sequential actions that require a CA put callback before going on to the next step.

 

Is there an easy/recommended way a number of actions to run in parallel and then wait for all the CA put callbacks?

 

Andrew C. Starritt | Principal Controls Engineer | Australian Synchrotron
p: (03) 8540 4164 | f: (03) 8540 4200
[email protected] | www.synchrotron.org.au
800 Blackburn Road, Clayton, Victoria 3168

 

 

 


References:
concurrent put callbacks Andrew C. Starritt
Re: concurrent put callbacks Mooney, Tim M.

Navigate by Date:
Prev: issue with either camonitor or pcaspy in 3.15? Jameson Graef Rollins
Next: Re: issue with either camonitor or pcaspy in 3.15? Wang Xiaoqiang
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: concurrent put callbacks Pearson, Matthew R.
Next: issue with either camonitor or pcaspy in 3.15? Jameson Graef Rollins
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
ANJ, 21 Dec 2017 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·