1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  <20192020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  <20192020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Receiving duplicate monitor values using CA PV Gateway
From: "Jemian, Pete R. via Tech-talk" <[email protected]>
To: "[email protected]" <[email protected]>
Date: Wed, 29 May 2019 20:32:59 +0000
Does your workstation have two active network interfaces?
Some modern Linux distributions install with a hypervisor that runs the 
Linux OS as a guest to that hypervisor.  The hypervisor has a management 
network interface and the linux OS has a separate one.  Each are on the 
same physical network connection.

On 2019-05-29 3:28 PM, William Layne via Tech-talk wrote:
> Hey all,
> 
> We are seeing duplicate values when first creating our subscriptions 
> through the CA Gateway. Is this normal? If not, does anyone know what 
> might be causing it?
> 
> Note: We are on EPICS V3.14.12.8 and Gateway 2.1.0
> 
> We see this in our applications and in tools such as camonitor. Here is 
> an example output from camonitor, for a heartbeat PV updating every second:
> 
> $ camonitor IOC1_HEARTBEAT
> IOC1_HEARTBEAT               2019-05-29 20:19:51.038659 7651
> IOC1_HEARTBEAT               2019-05-29 20:19:51.038659 7651
> IOC1_HEARTBEAT               2019-05-29 20:19:52.038654 7652
> IOC1_HEARTBEAT               2019-05-29 20:19:53.038657 7653
> ^C
> 
> Thanks,
> William 'Casey' Layne
> 
> 
> 

-- 
----------------------------------------------------------
Pete R. Jemian, Ph.D.                 <[email protected]>
Beam line Controls and Data Acquisition (BC, aka BCDA)
Advanced Photon Source,    Argonne National Laboratory
Argonne, IL  60439                    630 - 252 - 3189
-----------------------------------------------------------
       Education is the one thing for which people
          are willing to pay yet not receive.
-----------------------------------------------------------



Replies:
Re: Receiving duplicate monitor values using CA PV Gateway William Layne via Tech-talk
References:
Receiving duplicate monitor values using CA PV Gateway William Layne via Tech-talk

Navigate by Date:
Prev: Receiving duplicate monitor values using CA PV Gateway William Layne via Tech-talk
Next: Re: Receiving duplicate monitor values using CA PV Gateway William Layne via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  <20192020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Receiving duplicate monitor values using CA PV Gateway William Layne via Tech-talk
Next: Re: Receiving duplicate monitor values using CA PV Gateway William Layne via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  <20192020  2021  2022  2023  2024 
ANJ, 29 May 2019 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·