This is a bug. Would you like to create a report?
https://github.com/epics-base/pva2pva/
On 7/1/20 2:46 PM, Saeed via Tech-talk wrote:
> Hi,
>
> I'm trying to use DISP field for disabling the remote puts to my PV. It works as expected when I use CA but it seems like the IOC is neglecting this field and actually write to PV when the put is issued from pvAccess.
> 'test' is an ao record without any fields set in DCT and I use EPICS R7.0.4 here.
>
> ❯ caput test 10
> Old : test 0
> New : test 10
>
> ❯ pvput test.DISP 1
> Old : 2020-07-01 23:25:09.008 0
> New : 2020-07-01 23:25:09.008 1
> ❯ caput test 20
> Old : test 10
> CA.Client.Exception...............................................
> Warning: "Channel write request failed"
> Context: "op=1, channel=test, type=DBR_STRING, count=1, ctx="test""
> Source File: ../oldChannelNotify.cpp line 158
> Current Time: Wed Jul 01 2020 23:25:34.720217912
> ..................................................................
> New : test 10
> ❯ pvput test 20
> Old : 2020-07-01 23:25:09.008 10
> New : 2020-07-01 23:25:42.116 20
>
> Any thoughts?
>
> Thanks,
> Saeed
>
- Replies:
- Re: DISP field in pvAccess Saeed via Tech-talk
- References:
- DISP field in pvAccess Saeed via Tech-talk
- Navigate by Date:
- Prev:
DISP field in pvAccess Saeed via Tech-talk
- Next:
Re: DISP field in pvAccess Saeed via Tech-talk
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
<2020>
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
DISP field in pvAccess Saeed via Tech-talk
- Next:
Re: DISP field in pvAccess Saeed via Tech-talk
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
<2020>
2021
2022
2023
2024
|