1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  <20202021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  <20202021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: DISP field in pvAccess
From: Michael Davidsaver via Tech-talk <tech-talk at aps.anl.gov>
To: Saeed <saeeed3715 at gmail.com>
Cc: tech-talk at aps.anl.gov
Date: Wed, 1 Jul 2020 15:06:44 -0700
This is a bug.  Would you like to create a report?

https://github.com/epics-base/pva2pva/


On 7/1/20 2:46 PM, Saeed via Tech-talk wrote:
> Hi,
> 
> I'm trying to use DISP field for disabling the remote puts to my PV. It works as expected when I use CA but it seems like the IOC is neglecting this field and actually write to PV when the put is issued from pvAccess.
> 'test' is an ao record without any fields set in DCT and I use EPICS R7.0.4 here.
> 
>     ❯ caput test 10
>     Old : test                           0
>     New : test                           10
> 
>     ❯ pvput test.DISP 1
>     Old : 2020-07-01 23:25:09.008  0
>     New : 2020-07-01 23:25:09.008  1
>     ❯ caput test 20
>     Old : test                           10
>     CA.Client.Exception...............................................
>         Warning: "Channel write request failed"
>         Context: "op=1, channel=test, type=DBR_STRING, count=1, ctx="test""
>         Source File: ../oldChannelNotify.cpp line 158
>         Current Time: Wed Jul 01 2020 23:25:34.720217912
>     ..................................................................
>     New : test                           10
>     ❯ pvput test 20
>     Old : 2020-07-01 23:25:09.008  10
>     New : 2020-07-01 23:25:42.116  20
> 
> Any thoughts?
> 
> Thanks,
> Saeed
> 


Replies:
Re: DISP field in pvAccess Saeed via Tech-talk
References:
DISP field in pvAccess Saeed via Tech-talk

Navigate by Date:
Prev: DISP field in pvAccess Saeed via Tech-talk
Next: Re: DISP field in pvAccess Saeed via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  <20202021  2022  2023  2024 
Navigate by Thread:
Prev: DISP field in pvAccess Saeed via Tech-talk
Next: Re: DISP field in pvAccess Saeed via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  <20202021  2022  2023  2024 
ANJ, 02 Jul 2020 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·