record(ai, "AI0") {
field(LINR,"LINEAR")
field(EGUF,"32767")
field(EGUL,"-32768")
}
The PLC the value is 1003.124 in mBar, i have to display as 1.0031 Bar.
As you are using linear conversion already, wouldn't setting EGUF to 32.767 and EGUL to -32.768 result in a VAL that is smaller by a factor of 1000?
Cheers, ~Ralph