1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  <20202021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  <20202021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: read RVB and VAL don't match when moving smarAct motors without encoders
From: Juliane Reinhardt via Tech-talk <tech-talk at aps.anl.gov>
To: "Peterson, Kevin M." <kmpeters at anl.gov>, "tech-talk at aps.anl.gov" <tech-talk at aps.anl.gov>
Date: Thu, 12 Nov 2020 10:17:11 -0800
Hi Kevin,

thanks for your reply. I'm not sure what you mean by GST, GA or GP commands. However, we tried to communicate with the smarAct motors via the vendor software and did not get very informative feedback. (Same return value no matter what motor/controller we were using) Is there a way to get for feedback in EPICS, like a debug mode?

Best,
Juliane

On 11/11/20 16:05, Peterson, Kevin M. wrote:
Juliane,

How does the MCS controller respond to the GST, GA and GP commands for
an axis without an encoder?  It should be possible to send them using an
asyn record or a terminal in the vendor software.

The MCS driver assumes every axis will have a sensor and sets the motor
record's problem bit if the GST command returns an error.

Kevin

On 11/11/20 4:14 PM, Juliane Reinhardt via Tech-talk wrote:
Dear EPICS team,

I have recently been setting up smarAct MCS controllers for a couple of
smarAct motors, some of them have encoders and some don't. The 2 motors
that don't have encoders don't move although they are connected properly
(I assume). When I do "caput motor.VAL 0.5" I get the feedback for old
and new VAL and when I check with "caget motor.VAL" it matches. However,
the actual "caget motor.RBV" does not change accordingly and the motor
did not move.

What is required to move motors without an encoder in this case?

Thanks,
Juliane


--
Juliane Reinhardt, PhD
Project Scientist | ALS Computing Group
Blg. 15-337E | phone: 510-486-4313
jreinhardt at lbl.gov
Lawrence Berkeley National Lab


References:
read RVB and VAL don't match when moving smarAct motors without encoders Juliane Reinhardt via Tech-talk
Re: read RVB and VAL don't match when moving smarAct motors without encoders Peterson, Kevin M. via Tech-talk

Navigate by Date:
Prev: Re: read RVB and VAL don't match when moving smarAct motors without encoders Peterson, Kevin M. via Tech-talk
Next: Re: read RVB and VAL don't match when moving smarAct motors without encoders Mark Rivers via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  <20202021  2022  2023  2024 
Navigate by Thread:
Prev: Re: read RVB and VAL don't match when moving smarAct motors without encoders Peterson, Kevin M. via Tech-talk
Next: Re: read RVB and VAL don't match when moving smarAct motors without encoders Mark Rivers via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  <20202021  2022  2023  2024 
ANJ, 12 Nov 2020 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·