On 5/5/23 11:18 AM,
japanisverylittle--- via Tech-talk wrote:
how to explain this? Why does Input_1 run twice at 10 Hz?
The original intention was to show an example where two records with
SCAN=.1 second (i.e. Output_1 and Calculation_2) would both ask for
the Input_1 record to process using the PP (Process Passive)
mechanism that record links provide, thus Input_1 would be triggered
twice in every 10Hz cycle.
However there is a mistake in the diagram; the Output_1.DOL link
needs to be marked with the PP flag but as drawn it is flagged with
NPP instead, so as drawn the Output_1 record will never actually
request the Calculation_1 record to be processed at all, thus the
Input_1 record will only process at 10Hz.
Was that what you were asking?
- Andrew
--