1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  <2025 Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  <2025
<== Date ==> <== Thread ==>

Subject: Re: archiver appliance and CA -> PVA
From: Michael Davidsaver via Tech-talk <tech-talk at aps.anl.gov>
To: Pierrick M Hanlet <hanlet at fnal.gov>
Cc: "tech-talk at aps.anl.gov" <tech-talk at aps.anl.gov>
Date: Wed, 29 Jan 2025 21:46:56 -0800
On 1/29/25 14:32, Pierrick M Hanlet via Tech-talk wrote:
Greetings,
We are working toward going full PVA.  We've also recently upgraded the
archiver appliance to 2.0.5
and configured it for PVA.

However, we have a number of PVs for which we've been collecting data
for several years, and these
were originally configured with CA.  The IOCs have been restructured
with PVXS and with CA turned
off with EPICS_IOC_IGNORE_SERVERS=rsrv.  From the mgmt web page for the
AA, I see that these
PVs are not connected.  Furthermore, even explicity archiving them with
pva:// they still won't
connect.  Apart from reverting back to CA, what can I do so that they
connect to the AA with PVA?

As it happens, I was recently asking this question.

All per-PV configuration lives in the associated RDB.
Mostly in the PVTypeInfo table, typeInfoJSON column.
Each of these JSON blobs has a key boolean 'usePVAccess'.

For fun, I tried simply changing this key for a couple of
scalar double PVs.  I was a little concerned that these
might show up as Type Change events, which AA does not
handle.  However, in this case it did not.  So all is well.

I still would caution on simply making a bulk change.
It might be a good idea to eg. make a copy of the
configuration and MTS to start up another instance and
check if everything connects, no type changes occur, and
that you are able to query across the boundary.


Replies:
Re: archiver appliance and CA -> PVA Ralph Lange via Tech-talk
References:
archiver appliance and CA -> PVA Pierrick M Hanlet via Tech-talk

Navigate by Date:
Prev: Re: MRF kernel modules not seeing hardware Han Lee via Tech-talk
Next: Re: archiver appliance and CA -> PVA Ralph Lange via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  <2025
Navigate by Thread:
Prev: archiver appliance and CA -> PVA Pierrick M Hanlet via Tech-talk
Next: Re: archiver appliance and CA -> PVA Ralph Lange via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  <2025
ANJ, 30 Jan 2025 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions ·
· Download · Search · IRMIS · Talk · Documents · Links · Licensing ·