No, not inside the mbbiDirect.
To get the single bit description (and alarm severity/status, and value strings, ...) add a biRecord for each bit and point its input link to the appropriate bit field of the mbbiDirectRecord. If you make that input link CP or CPP, the single bit record will only process when the value of that bit changes.
Cheers, ~Ralph