1994  1995  1996  <19971998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  <19971998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Problem with VMS Multinet 4.0RevB - Channel Access Connects
From: [email protected]
To: [email protected]
Date: Wed, 01 Oct 1997 15:32:51 -0700 (PDT)
Hello -

Just a heads-up for people using VMS channel access clients.
Recently we upgraded to Multinet 4.0RevB on our VMS systems.  After
this upgrade, we were no longer able to connect with IOCs on the
same subnet and were forced to list IOCs in EPICS_CA_ADDR_LIST
until we installed a kernal-update ECO kit from Cisco.  This ECO fixed 
a problem with invalid checksum generation for UDP packets (the error
occurred when they tried to fix some problems with the way Microsoft
does DHCP).

Stephanie Allison  [email protected]

Navigate by Date:
Prev: Serial comms solution Peregrine McGehee
Next: Re: EPICs on PC Kay-Uwe Kasemir
Index: 1994  1995  1996  <19971998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Serial comms solution Peregrine McGehee
Next: Re: EPICs on PC Kay-Uwe Kasemir
Index: 1994  1995  1996  <19971998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 10 Aug 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·