On 9/13/16 4:49 AM, l123173 wrote:
> I got the "IDN?" output when the IOC started ( I saw the output
> with serial tool ), so I think the IOC worked fine.
> But I do not know how to do it then. For example, I do not know
> how to execute the command "ORG" or any other command of Kohzu controller.
The SC-800 support prints the output of the "IDN?" command during
motor_init() using sprintf().
The "ORG" command gets sent to the controller when a "1" is written to
the motor record's HOMF or HOMR field. This is usually done with a
channel-access client (caput, MEDM, CSS-BOY, caQtDM, EDM). It can also
be done from the IOC's shell using the "dbpf" command:
epics> help dbpf
dbpf 'record name' value
epics> dbpf IOC:m1.HOMR 1
DBR_SHORT: 1 0x1
Kevin
- References:
- motor command in synApps l123173
- Navigate by Date:
- Prev:
RE: motor command in synApps Mark Rivers
- Next:
Question about display history data in the form of data reports table in CSS boy opi ? lzf neu