EPICS Controls Argonne National Laboratory

Experimental Physics and
Industrial Control System

1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  <20182019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  <20182019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: pvPut error message by Sequencer
From: Andrew Johnson <[email protected]>
To: Simon Reiter <[email protected]>, <[email protected]>
Date: Tue, 30 Jan 2018 12:34:18 -0600
Hi Simon,

On 01/30/2018 09:41 AM, Simon Reiter wrote:
> using caput results in the same error message.
> I added the OMSL field with "supervisory" to the binary output record,
> but still fails.
> 
> Since I do not care, if it is output or input PV, I can switch. But it
> would be nice, to understand this problem.
It's a known internal bug in Base-3.16.1 which happened while making
link types extensible. Ralph pointed you to the Known Problems page; it
links to https://epics.anl.gov/base/R3-16/1-docs/msg503.patch which
should fix this issue if you apply the patch to your copy of Base and
rebuild.

HTH,

- Andrew

-- 
Arguing for surveillance because you have nothing to hide is no
different than making the claim, "I don't care about freedom of
speech because I have nothing to say." -- Edward Snowdon

References:
Scanning on event number fails with EPICS 3.16 Simon Reiter
pvPut error message by Sequencer Simon Reiter
Re: pvPut error message by Sequencer Benjamin Franksen
Re: pvPut error message by Sequencer Simon Reiter

Navigate by Date:
Prev: Re: Scanning on event number fails with EPICS 3.16 Michael Davidsaver
Next: Re: Scanning on event number fails with EPICS 3.16 Andrew Johnson
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  <20182019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: pvPut error message by Sequencer Simon Reiter
Next: Re: Scanning on event number fails with EPICS 3.16 Benjamin Franksen
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  <20182019  2020  2021  2022  2023  2024 
ANJ, 30 Jan 2018 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·