1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  <20212022  2023  2024  2025  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  <20212022  2023  2024  2025 
<== Date ==> <== Thread ==>

Subject: RE: [EXTERNAL] Data Browser (phoebus) auto data fetching from an Archiver Appliance
From: BENEDETTI Florian via Tech-talk <tech-talk at aps.anl.gov>
To: "Hartman, Steven" <hartmansm at ornl.gov>
Cc: "tech-talk at aps.anl.gov" <tech-talk at aps.anl.gov>
Date: Mon, 25 Oct 2021 07:34:39 +0000

Hello,


Thanks for your clear explanation.


The ioc runs on computer A and Archiver Appliance is installed on computer B. B is also a bridge between the experiment network and our internal network. CS Studio is installed on several computers on our internal network for monitoring purpose. I didn't want to expose directly PVs on our internal network for safety reasons, so I tried to used the Archiver for allowing users to monitor the experiment on our internal network .


I guess that deploying a PV gateway on B is a better solution.



De : Hartman, Steven <hartmansm at ornl.gov>
Envoyé : vendredi 22 octobre 2021 15:50:11
À : BENEDETTI Florian
Cc : tech-talk at aps.anl.gov
Objet : Re: [EXTERNAL] Data Browser (phoebus) auto data fetching from an Archiver Appliance
 


On Oct 22, 2021, at 8:38 AM, BENEDETTI Florian via Tech-talk <tech-talk at aps.anl.gov> wrote:

I would like to perform live plotting data with the Phoebus Data Browser from an Archiver Appliance instead of PVs. But it does not work as intended. I have to manually refresh the plot in order to get new data, otherwise the curve stuck with the last value (as shown in the screenshot). I tried to set scan as periodic instead of monitor but the same behavior is observed.


Typically, the data browser will get the historic data from the archiver, and then in-fill “live” data from Channel Access or PVAccess going forward, rather than periodically polling the archiver for updates. (The “periodic” and “monitor” settings refer to the CA subscription.) 

Can your client read the PV directly? 

-- 
Steven Hartman
hartmansm at ornl.gov




References:
Data Browser (phoebus) auto data fetching from an Archiver Appliance BENEDETTI Florian via Tech-talk
Re: [EXTERNAL] Data Browser (phoebus) auto data fetching from an Archiver Appliance Hartman, Steven via Tech-talk

Navigate by Date:
Prev: Re: Measurement Computing USB-1608G_2AO support Dudley, David via Tech-talk
Next: RE: Measurement Computing USB-1608G_2AO support Mark L Rivers via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  <20212022  2023  2024  2025 
Navigate by Thread:
Prev: Re: [EXTERNAL] Data Browser (phoebus) auto data fetching from an Archiver Appliance Hartman, Steven via Tech-talk
Next: undefine variable in RELEASE.local Pearson, Matthew R. via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  <20212022  2023  2024  2025 
ANJ, 26 Oct 2021 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions ·
· Download · Search · IRMIS · Talk · Documents · Links · Licensing ·