1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  <20222023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  <20222023  2024 
<== Date ==> <== Thread ==>

Subject: Re: StreamDevice return state error
From: "Zimoch Dirk \(PSI\) via Tech-talk" <tech-talk at aps.anl.gov>
To: "kasemirk at ornl.gov" <kasemirk at ornl.gov>, "patrick.e.barrett at boeing.com" <patrick.e.barrett at boeing.com>, "tech-talk at aps.anl.gov" <tech-talk at aps.anl.gov>
Date: Wed, 29 Jun 2022 12:40:39 +0000
On Wed, 2022-06-29 at 12:24 +0000, Kasemir, Kay wrote:
> Hi:
> 
> > > > The error "Record does not accept input" happens when you send a string (parsed with %s) to a record with an
> enum
> > > > VAL
> > > > like your mbbi, but the string does not match any of the enum strings in the record.
> > > > As your record only has "STANDBY", "OPERATE" and "SELFTEST", it does not accept the input "MONITOR".
> > > The mbbi should be in INVALID/CALC alarm state after that.
> > Except.... that your record is "I/O Intr". Such records get all the available input but process only matching input.
> > Non-matching input is silently ignored. That is by design how StreamDevice implements I/O Intr.
> 
> That all makes sense.
> SCAN=I/O Intr checks everything but only reacts on match.
> Anything else is assumed to be meant for some other record and thus ignored.
> 
> Maybe the issue could be avoided by changing the message from
>   error .. does not accept input 'MONITOR'
> to something like
>    info .. value 'MONITOR' ignored because outside of expected values.
> ?
> 
> Cheers,
> Kay


Actually I think, the error message should be suppressed for "I/O Intr" records.
And what you said for all others.

Dirk

References:
StreamDevice return state error Barrett (US), Patrick E via Tech-talk
Re: StreamDevice return state error Zimoch Dirk (PSI) via Tech-talk
Re: StreamDevice return state error Zimoch Dirk (PSI) via Tech-talk
Re: StreamDevice return state error Zimoch Dirk (PSI) via Tech-talk
Re: StreamDevice return state error Kasemir, Kay via Tech-talk

Navigate by Date:
Prev: Re: StreamDevice return state error Kasemir, Kay via Tech-talk
Next: Re: [EXTERNAL] Re: Phoebus connection to alarm server / Kafka Kasemir, Kay via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  <20222023  2024 
Navigate by Thread:
Prev: Re: StreamDevice return state error Kasemir, Kay via Tech-talk
Next: RE: StreamDevice return state error Barrett (US), Patrick E via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  <20222023  2024 
ANJ, 14 Sep 2022 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·