1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  <20232024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  <20232024 
<== Date ==> <== Thread ==>

Subject: Re: mvme6100 maxv controller maxvsetup
From: Mark Rivers via Tech-talk <tech-talk at aps.anl.gov>
To: whitetiger1123 <holyeongbaeg at gmail.com>
Cc: "tech-talk at aps.anl.gov" <tech-talk at aps.anl.gov>
Date: Thu, 2 Mar 2023 10:18:12 +0000
Those errors do not mean that the system could not find the MAXv boards. They mean that the autosave system could not find your motor records. That probably means that there was a syntax error loading the motor records, or that you used a different record prefix when loading the records than you did in your auto_serrings.req.

This command at the IOC shell will list all of the motor records:

dbl(“motor”)

This command will show the status of the MAXv cards:

dbior 

Mark


Sent from my iPhone

On Mar 2, 2023, at 1:04 AM, whitetiger1123 via Tech-talk <tech-talk at aps.anl.gov> wrote:



Hi,

Before I ask a question, I would like to thank the epics tech talk for helping me. I’m a beginner in epics and RTOS, but I was able to come to this step with a lot of help. Really appreciate it.

I try to boot MVME6100 with epics st.cmd, MAXv controller. But it shows me a error like this :

Done executing startup script 'host:/usr/local/epics_motor/synApps_5_8/support/motor-6-9/iocBoot/SX_PTL_motor/st2.cmd'.

-> save_restore: connect failed for channel 'BL:SX:EH:ATT1:M1.DVAL'

save_restore: connect failed for channel 'BL:SX:EH:ATT1:M1.DIR'

save_restore: connect failed for channel 'BL:SX:EH:ATT1:M1.DESC'

    ….

    …

 

save_restore: connect failed for channel 'BL:SX:EH:ATT1:M2.SREV'

save_restore: connect failed for channel 'BL:SX:EH:ATT1:M2.UREV'

save_restore: connect failed for channel 'BL:SX:EH:ATT1:M2.CNEN'

SX_PTL_settings2.sav: 0 of 106 PV's connected

 

So I think this error is related to st.cmd, wrong set address about MAXvSetup.(I guess)

 

I set up this st.cmd maxvsetup like this:

MAXvSetup(1, 16, 0x1000, 0, 5, 10)

 

And my Maxv controller jumper set is like this:

J12 Mode: A16

J12 IRQ : IRQ5

J13 left : A29, A30, A31

J13 right : AM1, AM2, AM4

 

I set the 8 jumpers on the left of J13 like this and put a value MAXvSetup(1, 16, 0x1000, 0, 5,10). I read Maxv User Manual as well, but I still don’t understand about this.. Do you have any solution about this?

 

 


References:
mvme6100 maxv controller maxvsetup whitetiger1123 via Tech-talk

Navigate by Date:
Prev: EPICS Collaboration meeting - registration is now open Pierrick M Hanlet via Tech-talk
Next: pasynOctetSyncIO error reading image status=4 Sintschuk, Michael via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  <20232024 
Navigate by Thread:
Prev: mvme6100 maxv controller maxvsetup whitetiger1123 via Tech-talk
Next: Phoebus OPC UA plugin William F Badgett Jr via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  <20232024 
ANJ, 02 Mar 2023 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·