> Just changing stat and sevr is not a valid solution because there
> may be other things wrong (value exceeds HIHI for example).
Perhaps all we need to do is set stat and sevr to no alarm when we
start rec init and then call the function alarm() in AO rec sup
at the end of rec init to compute the correct status and severity.
This will take care of the HIHI, HIGH, LOW, LOWLOW, and UDF
alarm conditions.
Jeff
______________________________________________________________________
Jeffrey O. Hill Internet [email protected]
LANL MS H820 Voice 505 665 1831
Los Alamos, NM 87545 USA FAX 505 665 5107
- Navigate by Date:
- Prev:
Re: Internal type conversion in Epics Marty Kraimer
- Next:
Internal type conversion in EPICS Andy Foster