1994  1995  1996  1997  1998  1999  2000  2001  2002  <20032004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  <20032004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020 
<== Date ==> <== Thread ==>

Subject: RE: stringIn record monitors
From: "Mark Rivers" <rivers@cars.uchicago.edu>
To: "Bill Cruise" <cruise@cfht.hawaii.edu>, <tech-talk@aps.anl.gov>
Date: Tue, 1 Apr 2003 21:52:20 -0600
Hi Bill,

It looks like the stringin record never posts monitors if the value has not changed.  

A couple of options:

- Make a simple database where the stringin record forward links to another record that does post monitors every time it processes.  You can put a monitor on that record, and whenever it posts an event then you know the stringin record has received new input, so you can read it.

- Use my generic serial record http://cars9.uchicago.edu/software/recSerial.html
  which always posts monitors on new input.  It only works with mpfSerial device support, however.

Mark Rivers


Navigate by Date:
Prev: stringIn record monitors Bill Cruise
Next: Re: stringIn record monitors Brian McAllister
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  <20032004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020 
Navigate by Thread:
Prev: Re: stringIn record monitors Brian McAllister
Next: Re: stringIn record monitors Andrew Johnson
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  <20032004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020 
ANJ, 10 Aug 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·