Release 2-1 of the EPICS "modbus" module is now available. This is from
the release notes:
- Bug fix. Non-automatic connection to the Modbus server uses
pasynCommonSyncIO->connectDevice(). The pasynUser being used for that
operation was being created with pasynOctetSyncIO->connect(). That was
always an error, it must be created with pasynCommonSyncIO->connect().
This error became serious with asyn R4-14, and non-automatic connection
no longer worked.
- Previous releases of modbus recommended setting NoAutoConnect=1 when
configuring the TCP or serial port. That was probably because of
problems in connection management in earlier versions of asyn. With asyn
R4-14 this is no longer necessary, and NoAutoConnect=0, the normal
default, can be used with no problems. The example scripts Koyo1.cmd and
Koyo2.cmd in the iocBoot directory have been changed to enable automatic
connection to the IP or serial driver.
Thanks to Zen Szalata of SLAC for finding this bug.
The release notes are here:
http://cars.uchicago.edu/software/epics/modbusReleaseNotes.html
The documentation is here:
http://cars.uchicago.edu/software/epics/modbusDoc.html
The tar file is here:
http://cars.uchicago.edu/software/pub/modbusR2-1.tgz
Please let me know of any problems or questions.
Cheers,
Mark
- Navigate by Date:
- Prev:
build streamDevice 2-4 error Ding Jianguo
- Next:
mca R6-12-2 available Mark Rivers
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
<2010>
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: build streamDevice 2-4 error Rod Nussbaumer
- Next:
mca R6-12-2 available Mark Rivers
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
<2010>
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
|