Hello Lynn,
Eric got this just before I could respond...
Let me add; Always look for the 1st error message in the startup
script.
Ron
On 2/7/2017 10:18 AM, Eric Norum wrote:
As the error message notes, you’re missing the TCP port number to
which you wish to connect. The port number is not optional.
drvAsynIPPortConfigure("L0","192.168.1.120",0,0,0)
drvAsynIPPortConfigure:
"192.168.1.120" is not of the form
"<host>:<port>[:localPort] [protocol]"
|
- References:
- LAN asyn connection error lynn
- Re: LAN asyn connection error Eric Norum
- Navigate by Date:
- Prev:
Re: LAN asyn connection error Eric Norum
- Next:
RE: How to support a new stepper motor controller? Mark Rivers