1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  <20212022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  <20212022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: [EXTERNAL] Data Browser (phoebus) auto data fetching from an Archiver Appliance
From: "Hartman, Steven via Tech-talk" <tech-talk at aps.anl.gov>
To: BENEDETTI Florian <florian.benedetti at cea.fr>
Cc: "tech-talk at aps.anl.gov" <tech-talk at aps.anl.gov>
Date: Fri, 22 Oct 2021 13:50:11 +0000


On Oct 22, 2021, at 8:38 AM, BENEDETTI Florian via Tech-talk <tech-talk at aps.anl.gov> wrote:

I would like to perform live plotting data with the Phoebus Data Browser from an Archiver Appliance instead of PVs. But it does not work as intended. I have to manually refresh the plot in order to get new data, otherwise the curve stuck with the last value (as shown in the screenshot). I tried to set scan as periodic instead of monitor but the same behavior is observed.


Typically, the data browser will get the historic data from the archiver, and then in-fill “live” data from Channel Access or PVAccess going forward, rather than periodically polling the archiver for updates. (The “periodic” and “monitor” settings refer to the CA subscription.) 

Can your client read the PV directly? 

-- 
Steven Hartman
hartmansm at ornl.gov




Replies:
RE: [EXTERNAL] Data Browser (phoebus) auto data fetching from an Archiver Appliance BENEDETTI Florian via Tech-talk
References:
Data Browser (phoebus) auto data fetching from an Archiver Appliance BENEDETTI Florian via Tech-talk

Navigate by Date:
Prev: Re: Re:RE: motor module make error Mark Rivers via Tech-talk
Next: Re: motor module make error Kevin Peterson via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  <20212022  2023  2024 
Navigate by Thread:
Prev: Data Browser (phoebus) auto data fetching from an Archiver Appliance BENEDETTI Florian via Tech-talk
Next: RE: [EXTERNAL] Data Browser (phoebus) auto data fetching from an Archiver Appliance BENEDETTI Florian via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  <20212022  2023  2024 
ANJ, 25 Oct 2021 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·