1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  <20052006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  <20052006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Logarithmic conversion / Breakpoint tabes
From: Rolf Keitel <[email protected]>
To: tech_talk <[email protected]>
Date: Wed, 30 Mar 2005 10:54:44 -0800
We have something similar, but really weird, with ion gauge controllers by Varian, which give a 0-10V readback with 1 V / pressure decade. Within the decade, however, the pressure readback is linear!!.
We use an analog record to convert the raw ADC value to voltage, then follow with a subroutine record, which does the funny calculation.
- rolf -


Gavin Smith wrote:

Hello All,

I have an Ai record which gets raw data from a pressure (vacuum?) sensor measured by the PLC. The raw data ranges from 0 to 256000 and represents a Torr of 1e-11 through to 1e-3. I am wanting to convert this into the engineering units, but as far as I can see only linear styles of conversion are supported. I could make a breaktable with some values in it, but if I understand correctly the gaps between the points will be interpolated linearly, and will therefore suffer some error.

In addition to inputs, I need to have a couple of Ao's, representing maximum allowable pressures, etc. My current thinking is to have a calc record for each sensor to evaluate something like CALC,"exp(A/3200-4)", and for the outputs having an ai feeding a calc feeding an ao record for each one.

How are other people handling this in their systems? Extra records, big breakpoint tables or some other way?

Thanks,
Gavin Smith.

(I'll be away from the office till next week sometime, so don't think I'm snubbing anyone by not replying to them straight away).



--
+-------------------------------------------------+
| Rolf Keitel, TRIUMF         Tel: (604) 222-7453 |
| Group Leader ISAC Controls  Fax: (604) 222-7307 |
| and Electronics Development                     |
| Vancouver, B.C., Canada                         |
+-------------------------------------------------+


References:
Logarithmic conversion / Breakpoint tabes Gavin Smith

Navigate by Date:
Prev: RE: Digitel MPC - TSP - RS232 Interface Mark Rivers
Next: calcout ODLY field Geoff Savage
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  <20052006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Logarithmic conversion / Breakpoint tabes Steven Hartman
Next: Re: Logarithmic conversion / Breakpoint tabes Bernhard Kuner
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  <20052006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 02 Sep 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·