Hello Jerome,
I spoke too soon. Disregard my earlier message.
How is your MAXv AX axis configured?
- stepper motor with encoder feedback (PSE)
- servo (PSM)
- stepper without encoder (PSO)
This is from the 2nd arguement of the MAXvConfig()
call.
Ron
Ron Sluiter wrote:
Hello Jerome,
Yes, there appears to be a bug in the motor record associated with
setting
the state of the limit switch indicator (RA_HOME) in the MSTA field.
Currently, RA_HOME is not getting set in process_motor_info() if
EA_PRESENT and UEIP are true. That's not right, RA_HOME should
be set unconditionally.
I'll contact you as soon as I get a patch on the motor record web site.
Thanks for the catching this,
Ron
jerome HOSSELET wrote:
Hi all,
I use a OMS MAXV4000/ MOTOR R 6.3 / EPICS base 3.14.9 / ASYN 4.9 /
vxWorks 6.2 / CPU Motorola MVME5500-0161 - MPC 7457
My problem is :
On EDM , a status HOME is always on 0 . ( I click on STATUS but
nothing change)
I check with a personnal SMV function
SMV("AX RA") REQUEST AXIS STATUS
I have this response
recv_mess(): card#0 - MNNH
MAXV>MNNH<
A driver see a HOME but on EDM nothing changed
i try to caget "IOC:m1.ATHM" but it s always on 0
(I think that EPICS record was not updated)
how resolv this BUGs !!!
thanks per advance
JEROME HOSSELET
- References:
- MAXv problem update EPICS record jerome HOSSELET
- Re: MAXv problem update EPICS record Ron Sluiter
- Navigate by Date:
- Prev:
Re: How to introduce usage of genSub ? Tim Mooney
- Next:
Re: DMA Example Andrew Johnson
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
<2008>
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: MAXv problem update EPICS record Ron Sluiter
- Next:
DMA Example Szalata, Zenon M.
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
<2008>
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
|